ADEMCO VISTA-15P Series Руководство по программированию - Страница 8
Просмотреть онлайн или скачать pdf Руководство по программированию для Система безопасности ADEMCO VISTA-15P Series. ADEMCO VISTA-15P Series 17 страниц.
Также для ADEMCO VISTA-15P Series: Руководство по быстрой установке (2 страниц)
Configurable Zone Types Worksheets
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data
fields*182-*185. Configurable zone types 92 and 93 (VISTA-20P only) can only be programmed using the
downloader software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and
field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the
tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types.
ENTRY 1
(See note 5 for RF zones)
Response when system disarmed and zone is:
Intact EOL
RF zone normal
0 = normal
0 = normal
1 = alarm
4 = alarm
2 = trouble
8 = trouble
3 = fault
12 = fault
Entry 1 = EOL + Open
ENTRY 3
(See note 5 for RF zones)
Response when armed STAY and zone is:
Intact EOL
RF zone normal
0 = normal
0 = normal
1 = alarm
4 = alarm
2 = trouble
8 = trouble
3 = fault
12 = fault
Entry 3 = EOL + Open
ENTRY 5
(See note 5 for RF zones)
Response when armed AWAY and zone is:
Intact EOL
RF zone normal
0 = normal
0 = normal
1 = alarm
4 = alarm
2 = trouble
8 = trouble
3 = fault
12 = fault
Entry 5 = EOL + Open
ENTRY 7
Display Faults
Power Reset/
Verification
0 = show alarms
0 = no
when armed
4 = power reset
& disarmed
1 = don't show
12 = verification
alarms when
armed
(show
alarms, trbles,
faults when
disarmed)
3 = never show
any alarms,
trbles, faults
Entry 7 = fault display + power
reset/verification
ENTRY 9
Alarm Sounds
0 = none
0 = no
1 = steady
4 = yes
keypad
2 = steady bell
see fields *32,
and keypad
*33
3 = pulsing bell
and keypad
Entry 9 = alarm sounds + bell timeout + fire zone
www.PDF-Zoo.com
ENTRY 2
(See note 5 for RF zones)
Open
Shorted
RF zone N/A
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Entry 2 = Short + auto restore + vent zone
ENTRY 4
(See note 5 for RF zones)
Open
Shorted
RF zone N/A
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Entry 4 = Short + byp. disarmed + byp. armed
ENTRY 6
(See note 5 for RF zones)
Open
Shorted
RF zone N/A
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Entry 6 = Short + dial delay + fault delay
ENTRY 8
Use Entry
Delay 1/2
0 = no
1 = delay 1
after fault
2 = delay 2
(by code + OFF)
(see zone
type 16)
Entry 8 = entry delay 1/entry delay 2 + exit delay +
interior zone type
Use Bell
Respond as
Timeout
Fire Zone
0 = no
8 = yes
see zone type
09; see note 4
Auto
Restore
Vent Zone
0 = no
0 = no
4 = yes
8 = yes
Byp. when
Byp. when
disarmed
armed
0 = no
0 = no
4 = yes
8 = yes
Dial Delay
Fault Delay
(see field *50)
(see field *87)
0 = no
0 = no
4 = use delay
8 = use delay
see note 1
Use Exit
Respond as
Delay
Interior Type
0 = no
0 = no
4 = use exit
8 = yes
delay
see note 2
ENTRY 10
Trouble
Chime when
Sounds
Chime Mode On
0 = none
0 = no
1 = periodic
4 = yes
beep
2 = trouble
beeps
Entry 10 = trouble sounds + chime
– 8 –
Entries for Fields *182 and *184
Entry Zone Type 90
Zone Type 91
(field *182)
(field *184)
1
2
3
4
5
6
7
8
9
10
To calculate the value for each entry:
Simply add the values of the selected options
in each of the entry's columns (one option per
column). For example, to program Entry 2 for
"alarm response to short," "auto restore on,"
but not a "vent zone," enter 5 ("1" for alarm
short + "4" for auto restore yes + "0" for vent
zone no).
INTACT
OPEN
SHORTED
EOL
Zone Conditions Represented
in Entries 1-6
NOTES:
1. Do not use the "fault delay" option with a
configurable zone type if it is set for an
entry or exit delay, otherwise
unpredictable results may occur.
2. To create an interior type zone, select
"respond as interior zone type" (entry 8,
interior type = yes), and set zone
response to "fault" in entries 3-4 to ensure
fault displays; do not set as "normal,"
"alarm," or "trouble."
3. Do not set fire zones to respond as a
"fault" (entries 1-6), otherwise faults will
not display unless the [∗] key is pressed.
4. 4219/4229 modules must use EOLRs or
unpredictable results may occur.
5. RF Zones: The "open" option in entries 1,
3, and 5 is not applicable for RF zones.
Use the "intact EOL" option for normal RF
zone conditions and "shorted" for off-
normal RF zone conditions.
6. Zone-Doubling/Double-Balanced: A short
on either zone of a zone-doubled pair or
on a double-balanced zone causes a
tamper condition.
ZONE-003-V0