The 13310-3xx series Loudspeakers are certified by
UL as Audible-signal Appliances for Use in
Hazardous Locations
1)
Introduction
The 13310-3xx series are UL certified loudspeakers which
produce a loud warning signal in a hazardous area. The
loudspeakers are approved for use in Gas applications in
Class I Division 1 & 2 as well as Class I Zone 0, 1 and 2.
2)
Warnings
CAUTION
TO REDUCE THE RISK OF IGNITION OF
HAZARDOUS ATMOSPHERES:
DISCONNECT FROM SUPPLY BEFORE OPENING.
KEEP TIGHTLY CLOSED WHEN IN OPERATION.
WARNING
FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18
INCHES FROM ENCLOSURE.
EQUIPMENT MUST NOT BE INSTALLED WITH THE
HORN FACING UPWARDS OF HORIZONTAL.
ATTENTION
POUR REDUIRE LE RISQUE D'INFLAMMATION
DES ATMOSPHÈRES DANGEREUSES:
COUPER L 'ALIMENTATION AVANT OUVERTURE.
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT.
AVERTISSEMENT
CONDUITS DOIVENT ÊTRE SCELLÉS EN MOINS DE 18
POUCES.
ÉQUIPEMENT NE DOIT PAS ÊTRE INSTALLÉ AVEC
LE KLAXON TOURNÉE VERS LE HAUT DE
HORIZONTAL.
__________________________________________________________________________________________________________________
GAI-Tronics 3030 Kutztown Rd. Reading PA 19605 USA
Document No. 42004-502A
INSTRUCTION & SERVICE MANUAL
13310-3xx LOUDSPEAKERS
For Use In Hazardous Locations - Gas
3)
3.1 Class / Division Ratings for US and Canada
The 13310-3xx Loudspeakers comply with the following
standards for hazardous locations:
3.2 Class / Division Ratings for US & Canada
Installation must be carried out in compliance with the
National Electric Code / Canadian Electric Code.
3.3 Class / Zone ratings US and Canada
Class I Zone 1
Installation must be carried out in compliance with the
National Electric Code / Canadian Electric Code.
3.4 Ambient Temperature Range
−40ºC to +70ºC
3.5 Enclosure Ratings
The product is rated for ingress protection as follows:
IP rating per EN60529:
Type rating per UL50E / NEMA250: 4 / 4X / 3R / 13
3.6 Electrical Ratings
3.7 Frequency Range
4)
4.1 Safe Installation Requirements
The product must only be installed by suitably qualified
personnel in accordance with the latest issues of the
relevant standards.
The installation of the units must also be in accordance
with the NEC / CEC and any local regulations and should
only be carried out by a competent electrical engineer who
has the necessary training.
09-29-15
www.gai-tronics.com
Sheet 3 of 5
Ratings and Markings
UL 1203
CSA C22.2 NO. 30-M1986
The 13310-3xx Loudspeakers also comply with the
following standards for signaling equipment:
UL 1480
CSA C22.2 NO. 205-12
Class I Div 1
ABCD
IIC T6
Model No.
Input
13310-313
70V Line
13310-312
8 Ohm
13310-311
16 Ohm
All models: 400 Hz to 8000 Hz
Installation
Ta −40°C to +70°C
T6
Ta −40ºC to +70°C
IP66
Power
Max I/P
(Watts)
Volts
25
70
25
14.14
25
20