HID EDGE EVO EH400-K Руководство по установке - Страница 2

Просмотреть онлайн или скачать pdf Руководство по установке для Контроллер HID EDGE EVO EH400-K. HID EDGE EVO EH400-K 13 страниц. Standard networked controller

HID EDGE EVO EH400-K Руководство по установке
I N STALLATI ON GUI DE

Installation

1

Power Analysis

Before starting installation, determine which components will be used in the system and analyze
the power requirements to avoid over-loading the EDGE EVO Hi-O Networked Controller & Reader
(EH400-K).
The following steps illustrate sizing power requirements for the system.
Step    1
Identify System Components 
Identify the components that will be used in the system. A typical installation may include the following
components:
• Door Position Switch – Detects when the door is open or closed.
• Magnetic Lock – Holds the door locked.
• Request to Exit (REX) Switch – Unlocks the door when exiting the secured area.
• EDGE EVO Hi-O Standard Networked Controller (EH400-K) – Provides access control and manages
all peripherals around the door.
• iCLASS® Wiegand Reader – Provides entry into the secured area.
Step    2
Create System Layout
Using the components identified in Step    1 Identify System Componentscreate the system layout.
In this example, the EH400-K is connected to the remote server through an Ethernet connection and
manages door peripherals over the Hi-O bus. Controlling downstream door peripherals, the EH400-K is
a fully integrated single-door controller offering discrete I/O and Wiegand/Clock-and-Data interfaces
to external readers. The EH400-K receives inputs from the Door Position Switch and REX Switch to
drive the Magnetic Lock output.
Unprotected
cted
Area
Wiegan
Wiegand
Wiegand Reader
Door P
Door Position
Mag
Magnetic Lock
Protected Area
Ethernet Data
Swi
Switch
EH400-K
ne
REX Switch
Remote Area
Ethernet Switch
Physical Access
Control Server
(real-time functions
not required )
Page 2
An ASSA ABLOY Group brand
EDGE EVO
82000-921, Rev. D.3