HID EDGE EVO ESH400 Руководство по установке - Страница 3

Просмотреть онлайн или скачать pdf Руководство по установке для Контроллер HID EDGE EVO ESH400. HID EDGE EVO ESH400 12 страниц. Hi-o networked controller

HID EDGE EVO ESH400 Руководство по установке
82000-920, D.1
Step 3 - Analyze Power Requirements
A - Door Peripheral Operational Currents
For the door peripherals identified in "Step 1 - Identify System Components" on page 2, consult the vendor data
sheets to determine the operational current draw. Typical operational current draw is provided below.
Note: See individual peripheral data sheets for actual operational current draw.
Device
Door Position Switch
(For example, Securitron MSS)
Mag Lock
(For example, Securitron M32)
REX Switch
(For example, Securitron EEB)
Exit Alarm
(For example, Detex 411)
iCLASS Wiegand Reader
Consult HID datasheets for Hi-O enabled interface devices.
B - Match I/O Requirements to the Hi-O Interface Device
For the door peripherals identified in "Step 1 - Identify System Components" on page 2, the system requires
connection to a Hi-O interface device. In this example, the EDGE EVO Hi-O Edge Door Module (EDM-M) provides
general purpose I/O connectivity.
The Hi-O iCLASS reader does not require connection to the EDM-M and derives power and data connectivity from the
Hi-O CANbus directly.
Device
EDGE EVO Hi-O Door
Module EDM-M
*
Shared between each relay
** Each relay
The combined current requirement for the four door peripherals identified in "Step 1 - Identify System Components" on
page 2 is 413mA @ +12VDC,
or 273mA @ +24VDC.
The EDM-M provides sufficient power when the door peripherals are connected to the Strike/AUX relays configured for
unregulated output at +12VDC/+24VDC. Alternatively, connect the door peripherals to the Strike/AUX relays configured
for Dry contact.
The Hi-O iCLASS reader does not require connection to the EDM-M and derives power and data connectivity from the
Hi-O CANbus directly.
©2009 - 2012 HID Global Corporation. All rights reserved.
EDGE EVO Hi-O Networked Controller
Conditions
V
= 12VDC
in
V
= 24VDC
in
V
= 12VDC
in
V
= 24VDC
in
V
= 12VDC
in
V
= 24VDC
in
V
= 12VDC
in
V
= 24VDC
in
V
= 12VDC
in
Ports
Conditions
+12VDC unregulated (@+12VDC EDM-M input)
Strike / Aux
NC or NO
+24VDC unregulated (@+24VDC EDM-M input)
DC Output
+12VDC regulated (@+24VDC EDM-M input)
+12 to +24VDC External
Dry Jumpers
Typical Operational Current
15mA
15mA
300mA
150mA
28mA
38mA
70mA
70mA
150mA
I
out
700mA*
700mA*
310 mA*
2.00 Amp**
INSTALLATION GUIDE
EH400
3