RHINO Installation Instructions for PSS0524-100 Power Supply
READ INSTRUCTIONS BEFORE INSTALLING OR OPERATING THIS DEVICE. KEEP FOR FUTURE REFERENCE
1. Safety instructions
• To ensure sufficient convection cooling, always maintain a safety distance of M 20 mm (0.79 in) from all
ventilated surfaces while the device is in operation.
• The device is not recommended to be placed on low thermal conductive surface, for example, plastics.
• Note that the enclosure of the device can become very hot depending on the ambient temperature and load
of the power supply. Do not touch the device while it is in operation or immediately after power is turned OFF.
Risk of burning.
• Do not touch the terminals while power is being supplied. Risk of electric shock.
• Prevent any foreign metal, particles or conductors from entering the device through the openings during in-
stallation. It can cause electric shock, safety hazard, fire, and/or product failure.
• Warning: When connecting the device, secure GND connection before connecting L and N. When
disconnecting the device, remove the L and N connections before removing the GND connection.
2. Device description (Fig. 1)
(1) Input & Output terminal block connector (V1: 24VDC, V2: 5VDC)
(2) DC voltage adjustment potentiometer for V1: 24VDC
(3) DC OK indicatorLED (green)
3. Connection (Fig. 1)
The terminal block connector allows easy and fast wiring.
4. Mounting (Fig. 2)
A. Mounting holes for power supply assembly onto the mounting surface. Power supply shall be mounted on
minimum 2 mounting holes using M3 x 0.5 screw minimum 5 mm (0.19 in) length.
B. This surface belongs to customer's system or panel where the power supply is mounted.
C. Connector:
Use flexible (stranded wire) or solid wire 22–12 AWG. The torque at the connector shall not
exceed 1.3 Nm (11.3 in-lb). The insulation stripping length should not exceed 0.28 in or 7 mm.
Fork terminal recommended for stranded wire. Refer to figure 3.
5. Installation of Mounting Accessories (Fig. 4)
• Only use M3 screw m 6 mm through the base mounting holes. This is to keep a safety distance between the
screw and internal compontents.
• Refer to Figure 4: Recommended mounting tightening torque: 0.4 to 0.8 Nm (3.5 to 7 in-lb).
FOR TECHNICAL ASSISTANCE CALL 770-844-4200
.
Ventilated surface
Base surface
Figure 1 - Device Descriptions
Side Mounting (Vertical)
Figure 2 - Mounting
AutomationDirect
P/N V70GK004003 (22-18AWG)
V70GK004008 (16-14AWG)
V70GK004003 (12AWG)
or equivalent
Figure 3 - Wire Type
Figure 4 - Mounting Screw
Side surface
Top surface
3
2
1
Base Mounting (Vertical)
Side Mounting (Horizontal)
7mm
[0.28in]
Lug
Stripped wire
Mounting
Chassis of
accessories
the device
Mounting
screw
6mm max.