AutomationDirect SOLO SLM Series Краткое руководство по эксплуатации - Страница 2
Просмотреть онлайн или скачать pdf Краткое руководство по эксплуатации для Контроллер температуры AutomationDirect SOLO SLM Series. AutomationDirect SOLO SLM Series 4 страницы. Modular temperature controllers
Box Contents and Unpacking Instructions
4
• Unpack the SOLO SLM temperature controller from its shipping carton. Included in the carton is
the temperature controller, a 249 ohm resistor, and this Quick Start Guide.
• Inspect all equipment for completeness. If anything is missing or damaged, immediately call the
AutomationDirect returns department @ 1-800-633-0405.
• • Inspect the part number to ensure the model received matches the output type required.
SLM
Quick Start
Guide
5
Controller Dimensions
Dimensions
mm [in]
6
5
4
5
7
1
11
8
12
10
2
13
9
3
3
25.2
3.4
[0.99]
[0.13]
SLM1
5
4
3
4
6
10
7
9
1
8
2
2
25.2
3.4
60.0
[0.99]
[0.13]
[2.36]
SLM2
LED Display
6
1. When power is normal, POWER LED will be on.
2. After SLM is switched on, all LEDs will be on. The communication protocol will be displayed for one
second. See table below for LED values.
3. RUN LED is on when the controller is active.
4. ERROR LED is on when errors occur in input, memory or communication.
5. When an output is active, its corresponding output LED will be on.
6. AT LED flashes when PID parameters are being auto-tuned.
7. RX LED flashes when SLM receives communication signals. TX LED flashes when SLM sends out
communication signals. Communication protocol displayed on the LEDs after the power to the SLM
is switched on:
LED
2400
4800
AT
Off
Off
Off
Off
TX
RX
Off
On
LED
Parity
01
Off
Off
02
Off
On
LED
Modbus Format
Err
Off
On
LED
Stop Bits
RUN
Off
On
Terminal Identification
7
WARNING! ELECTRIC SHOCK DANGER
To prevent electric shock, do not connect AC
power to your device until all input and output
connections are completed.
SLM Temperature
Controller
249 ohm
resistor
SLM1
RUN/STOP switch
1
Wiring and Model
2
name
3
DIN rail clip
I/O terminals
LED indicators
4
5
LED indicators
Mounting hole
Mounting hole
6
60.0
Specification label Extension port
7
[2.36]
8
Extension port
Extension clip
9
Extension clip
DIN rail
Extension port
10
RS-485
communication
11
port
Extension clip
12
13
DC power input
Baud Rate
9600
19,200
38,400
Off
Off
On
On
On
Off
Off
On
Off
On
Off
Input and Outputs (SLM1 & SLM2 Front Terminals)
- -
- -
1
Tc
2
+ +
+ +
3
4
+ +
5
OUT2
6
- -
7
+ +
8
OUT1
- -
9
8
Alarm Output
SLM series offers 12 alarm modes. See the alarm table below for a description of types of alarm.
Mode
0
1
2
3
4
SLM2
Wiring and
Model name
DIN rail clip
5
I/O terminals
Specification
6
label
DIN rail
7
N/A
N/A
8
N/A
9
10
11
12
Note: AL-H and AL-L include AL1H, AL2H, AL1L and AL2L. When Output 1 is set to Alarm Output, use AL1H (1024H) and AL1L
(1025H). When Output 2 is set to Alarm Output, use AL2H (1026H) and AL2L (1027H).
Sensor Input
Power Input (SLM1 Bottom Terminals)
For 4-20 mA sensor input
install supplied 249 resistor.
1
1
Vin
in
2
2
4 - 20 mA
0 - 10 VDC
1
Install jumper when using
2-wire RTD
RS-485 (SLM1 Bottom Terminals)
2
3
2-wire RTD
1
1
2
2
3
Thermocouple (Tc)
3-wire RTD
Alarm Output
Alarm Type
Alarm Output Operation
No alarm
OFF
Alarm output will be enabled when the
temperature reaches upper and lower limits.
OFF
• Alarm will be enabled when the PV exceeds SV
+ AL-H or falls below SV – AL-L.
Alarm output will be enabled when the
temperature reaches the upper limit.
OFF
• Alarm will be enabled when the PV exceeds SV
+ AL-H.
Alarm output will be enabled when the
temperature reaches the lower limit.
OFF
• Alarm will be enabled when the PV falls below
SV – AL-L.
• Alarm will be enabled when the PV is between
OFF
SV + AL-L and SV – AL-L.
Alarm output will be enabled when the
temperature reaches the absolute value of the
OFF
upper and lower limits.
• Alarm will be enabled when the PV exceeds
AL-H or falls below AL-L.
Alarm output will be enabled when the
temperature reaches the absolute value of the
OFF
upper limit.
• Alarm will be enabled when the PV exceeds
AL-H.
Alarm output will be enabled when the
temperature reaches the absolute value of the
OFF
lower limit.
• Alarm will be enabled when the PV falls below
AL-L.
Standby upper/lower limit alarm
• Alarm will be enabled when the PV reaches SV
OFF
and exceeds SV + AL-H or falls below SV –AL-L.
Upper limit standby alarm
• Alarm will be enabled when the PV reaches SV
OFF
and exceeds SV + AL-H.
Lower limit standby alarm
• Alarm will be enabled when the PV reaches SV
OFF
and falls below SV – AL-L
Upper limit hysteresis alarm
• Alarm will be enabled when the PV exceeds SV
OFF
+ AL-H and disabled when the PV falls below
SV + AL-L.
Lower limit hysteresis alarm
ON
• Alarm will be enabled when the PV falls below
OFF
SV – AL-H and disabled when the PV exceeds
SV – AL-L.
24V
DC 21.6 to 26.4
0V
+ +
- -
ON
AL-L
SV
AL-H
ON
SV
AL-H
ON
AL-L
SV
ON
AL-L
SV
AL-H
ON
AL-L
AL-H
ON
AL-H
ON
AL-L
ON
SV
AL-L
AL-H
ON
SV
AL-H
ON
AL-L SV
ON
AL-L
AL-H
AL-H
AL-L