Chapter 2: Installation
2.7.1 - EMI Filters
All electronic equipment (including servo drives) generates high or low frequency noise during
operation, which interferes with peripheral equipment through conduction or radiation. With
an EMI filter and the correct installation, you can eliminate much of the interference. For better
performance, using an EMI filter to suppress the interference is recommended.
Servo Drive
Model
SV2A-2040
SV2A-2075
SV2A-2150
SV2A-2200
SV2A-2300
SV2A-2550
SV2A-2750
SV2A-2F00
General precautions for installation
To ensure the best performance of the EMI filter, apart from the instructions on installation
and wiring of servo drive, please observe the precautions below:
• The servo drive and EMI filter should be mounted on the same unpainted metal plate�
• The wiring should be as short as possible�
• The metal plate should be well grounded�
More specifications for mounting the servo drive are listed below:
• EN61000-6-4 (2001)
• EN61800-3 (2004) PDS of category C2
• EN55011+A2 (2007) Class A Group 1
Motor cable selection and installation precautions
The selection of motor cables (please refer to Appendix B Accessories) and installation
determines the performance of the EMI filter. Please follow the precautions below.
• Use a cable that has braided shielding (the effect of double shielding is better)�
• The shield on both ends of the motor cable should be grounded with the shortest cable
length and the largest contact area�
• Remove the any protective paint on the U-shape saddle EMC cable clamp and metal plate in
order to ensure good contact� Please see the figure below�
• A correct connection between the braided shielding of the motor cable and the metal plate
is required� The braided shielding on both ends of the motor cable should be fixed by the
EMC cable clamp U-shape saddle and metal plate� Please see the figure below for the correct
connection�
Page 2–10
Main Voltage Level
100-120VAC 1-phase
200-230VAC 1-phase
200-230VAC 3-phase
100-120VAC 1-phase
200-230VAC 1-phase
200-230VAC 3-phase
100-120VAC 1-phase
200-230VAC 1-phase
200-230VAC 3-phase
100-120VAC 1-phase
200-230VAC 1-phase
200-230VAC 3-phase
200-230VAC 3-phase
200-230VAC 3-phase
200-230VAC 3-phase
200-230VAC 3-phase
Recommended EMI Filter
Standard
Good Performance
Performance
Roxburgh
GS Series
EMF11AM21A
RES90F10
EMF11AM21A
RES90F10
EMF10AM23A
KMF306A
EMF27AM21B
RES90F16
EMF27AM21B
RES90F16
EMF10AM23A
KMF310A
EMF27AM21B
RES90S20
EMF27AM21B
RES90S20
EMF24AM23B
KMF318A
EMF27AM21B
RES90S30
EMF27AM21B
RES90S30
EMF24AM23B
KMF325A
EMF24AM23B
KMF336A
n/a
KMF350A
n/a
KMF350A
n/a
KMF3100A
SureServo2 User Manual – 1st Edition – 05/20/2021
High Performance
Roxburgh
MIF10
MIF10
MIF310
MIF16
MIF16
MIF310
MIF23
MIF23
MIF316
MIF330B
MIF330B
MIF323
MIF330B
MIF350
MIF350
MIF3100