Automationdirect.com Productivity 2000 P2-16AD-1 Руководство - Страница 2
Просмотреть онлайн или скачать pdf Руководство для Системы ввода/вывода Automationdirect.com Productivity 2000 P2-16AD-1. Automationdirect.com Productivity 2000 P2-16AD-1 8 страниц. Analog input
General Specifications
Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
800mW
Enclosure Type
Open Equipment
UL508 File E139594, Canada & USA
Agency Approvals
CE (EN61131-2*)
Module Keying to Backplane
Electronic
Module Location
Any I/O slot in a Productivity2000 System
ZIPLink Wiring System ONLY. See "Wiring Options" on
Field Wiring
page 5. Must use copper conductors 75ºC or equivalent.
See the "EU Directive" topic in the Productivity2000
EU Directive
Help File. Information can also be obtained at:
www.productivity2000.com
Connector Type
24-Pin Molex Style 43025-2400
Weight
90g (3.2 oz)
2
www.productivity2000.com
Input Specifications
Input Channels
16 sinking
Module Signal Input Range
0–20 mA
Signal Resolution
16-bit
Resolution Value of LSB
0–20 mA = 0.305μA per count
(least significant bit)
(1 LSB = 1 count)
Data Range
0 to 65535 counts
Input Type
Single-ended (1 common)
Maximum Continuous Overload
±31mA
Input Impedance
250Ω ±0.1% 1/4W
Filter Characteristics
Low Pass, -3dB @ 100Hz
4ms per channel
Sample Duration Time
(does not include ladder scan time)
All Channel Update Rate
112ms
Open Circuit Detection Time
Zero reading within 1s
Conversion Method
Successive approximation
Accuracy vs. Temperature
±25PPM / ºC maximum
0.1% of range
Maximum Inaccuracy
(including temperature drift)
±10 LSB maximum (±0.015% of range)
Linearity Error (end to end)
Monotonic with no missing codes
Input Stability and Repeatability
±10 LSB
Full Scale Calibration Error
±10 LSB maximum (±0.015% of range)
(not including offset)
Offset Calibration Error
±10 LSB maximum
Max Crosstalk
-76dB, ±10 LSB
Recommended Fuse (external)
Edison S500-32-R, 0.032 A fuse
External DC Power Required
24VDC (-20% / +25%) 35mA
Tech Support 770-844-4200