Automationdirect.com Productivity 2000 P2-16ADL-2 Руководство - Страница 2

Просмотреть онлайн или скачать pdf Руководство для Системы ввода/вывода Automationdirect.com Productivity 2000 P2-16ADL-2. Automationdirect.com Productivity 2000 P2-16ADL-2 8 страниц. Analog input

Automationdirect.com Productivity 2000 P2-16ADL-2 Руководство

General Specifications

Surrounding Air Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
1100mW max
Enclosure Type
Open Equipment
UL508 File E139594, Canada & USA
Agency Approvals
CE (EN61131-2*)
Module Keying to Backplane
Electronic
Module Location
Any I/O slot in a Productivity2000 System
Use ZIPLink Wiring System ONLY. See "Wiring Options"
Field Wiring
on page 5. Must use copper conductors 75°C or
equivalent
See the "EU Directive" topic in the Productivity Suite
EU Directive
Help File. Information can also be obtained at:
www.productivity2000.com
Terminal Type
24-point ZIPLink
Weight
102g (3.6 oz)
*Meets EMC and Safety requirements. See the D.O.C. for details.
2
www.productivity2000.com

Input Specifications

Input Channels
16
Module Signal Input Range
0-10 VDC
Signal Resolution
13-bit
Resolution of LSB
0-10VDC = 1.22mV per count (1LSB = 1 count)
(least significant bit)
Data Range
0-8191 counts
Input Type
Single-ended (1 common)
Maximum Continuous Overload
±100VDC
Input Impedance
>150kΩ
Filter Characteristics
Low Pass, -3dB @ 500Hz
6.25ms per channel
Sample Duration Time
(does not include ladder scan time)
All Channel Update Rate
25ms
Open Circuit Detection Time
Zero reading within 100ms
Accuracy vs. Temperature
±75PPM / ºC maximum
Conversion Method
Successive approximation
0.5% of range
Maximum Inaccuracy
(including temperature drift)
±0.036% of range
Linearity Error (end to end)
Monotonic with no missing codes
Input Stability and Repeatability
±0.024% of range
Full Scale Calibration Error
±0.097% of range
(including offset)
Offset Calibration Error
±0.097% of range
Max Crosstalk
4 counts / 0.048% of range
External 24VDC Power Required
24VDC (-20% / +25%), 35mA
Tech Support 770-844-4200