Automationdirect.com ACT050 Инструкции по установке
Просмотреть онлайн или скачать pdf Инструкции по установке для Преобразователь Automationdirect.com ACT050. Automationdirect.com ACT050 2 страницы. Act/actr series
Specifications
Output Signal
0-10 VDC or 4-20 mA (see Part Number Key)
Output Limit
ACTx-010
15 VDC
Units up to 200 A: 32 mA
ACTx-42L
Units from 200 A up to 2000 A: 23 mA
ACTRx-42L
23 mA
Frequency Range
ACTx-010
50-60 Hz (Sinusoidal)
ACTx-42L
20-100 Hz (Sinusoidal)
ACTRx-42L
10-400 Hz (All Wave forms)
Response Time To 90% of Step Change
ACTx-010
100 ms
Units up to 200 A: 300 ms
ACTx-42L
Units from 200 A up to 2000 A: 500 ms
ACTRx-42L
600 ms
Accuracy
ACTx-010
1% FS
ACTx-42L
1% FS
ACTRx-42L
1% FS
General
Power Supply,
-42L
24 VDC Nominal, 40 VDC Max.
Output Load,
-010
1 M recommended, 100 K : add 1.3% error
To 200 A: UL listed to 1270 VAC, Tested to 5kV
Isolation Voltage
Units 750 and 2000 A: 600 VAC
Case
UL 94V-0 Flammability rated thermoplastic
-4 to 122°F (-20 to 50° C) operating temperature
Environmental
0-95% RH, non-condensing humidity
UL 508 and cUL Listed, UL File E222847
Listings
CE Certified
Ranges & Maximum Amps - Input Maximums
MAXIMUM INPUT AMPS
MAXIMUM
MODEL
RANGE
CONTINUOUS
6 Seconds
ACT005
0 - 2 A
80 A
125 A
and
0 - 5 A
100 A
125 A
ACTR005
0 - 10 A
80 A
125 A
ACT050
and
0 - 20 A
110 A
150 A
ACTR050
0 - 50 A
175 A
215 A
0 - 100 A 200 A
300 A
ACT200
and
0 - 150 A 300 A
450 A
ACTR200
0 - 200 A 400 A
500 A
0 - 375 A 750 A
1500 A
ACT750
and
0 - 500 A 750 A
1500 A
ACTR750
0 - 750 A 750 A
1500 A
ACT2000
0 - 1000 A 2000A
4000 A
and
0 - 1333 A 2000A
4000 A
ACTR2000
0 - 2000 A 2000A
4000 A
A C T
005 - 42L - F
SENSOR TYPE:
T - Transducer, Average responding sinusoidal waveforms
TR - Transducer, True RMS, non sinusoidal waveforms
4 -20 mA output only
AC current operated
MAXIMUM
1 Second
250 A
250 A
250 A
300 A
400 A
600 A
800 A
1000 A
3505 Hutchinson Road, Cumming, GA 30040
3750 A
Phone: (800) 633-0405 or (770) 889-2858
3750 A
3750 A
10000 A
10000 A
10000 A
Part Number Key
CASE STYLE
F
-
F
x i
d e
C
o
e r
S
-
S
l p
- t i
C
o
e r
OUTPUT
S (
l o
d i
S
a t
e t
S
i w
c t
) h
0 - 10 to 10 VDC, self-powered
42L - 4 to 20 mA loop powered out
(requires 24 VDC power supply)
FULL SCALE RANGE:
005 - 2 A and 5 A
050 - 10, 20, 50 A
200 - 100, 150, 200 A
750 - 375, 500, 750 A
2000 - 1000, 1333, 2000A
AutomationDirect.com (ADC)
Fax: (770) 889-7876
ACT/R-v-mu-Inst - Rev 4 031 1 PN 291002129
ACT/ACTR SERIES
INSTALLATION
INSTRUCTIONS
Quick Start Guide
1. Run the wire to be monitored through
the aperture.
2. Mount the sensor to a surface, if
needed.
3. Connect output wiring.
A. Use up to 14 AWG copper
wires.
B. 10 VDC models: make sure
output load is at least 1 Mq.
C. 4-20 mA models: make sure
loop voltage is correct
4. Select Range. Choose correct range
by positioning the Range Jumper
(750/2000 series have a 3-position
switch rather than a jumper).