Aire-Flo 41 Руководство по установке - Страница 16
Просмотреть онлайн или скачать pdf Руководство по установке для Кондиционер Aire-Flo 41. Aire-Flo 41 18 страниц. 14 seer
Outdoor Unit
1 - Inspect component wiring for loose, worn or damaged
connections. Also check for any rubbing or pinching of
wires. Confirm proper voltage plus amperage outdoor
unit.
2 - Check the cleanliness of outdoor fan and blade
assemblies. Check condition of fan blades (cracks).
Clean or replace them, if necessary.
3 - Inspect base pan drains for debris and clean as
necessary.
4 - Inspect the condition of refrigerant piping and confirm
that pipes are not rubbing copper-to-copper. Also,
check the condition of the insulation on the refrigerant
lines. Repair, correct, or replace as necessary.
5 - Test capacitor. Replace as necessary.
6 - Inspect contactor contacts for pitting or burn marks.
Replace as necessary.
7 - Check outdoor fan motor for worn bearings/bushings.
Replace as necessary.
8 - Inspect and clean outdoor coils, if necessary and note
any damage to coils or signs of leakage.
NOTICE !
Failure to follow instructions will cause damage to
the unit.
This unit is equipped with an aluminum coil. Alu
minum coils may be damaged by exposure to solu
tions with a pH below 5 or above 9. The aluminum
coil should be cleaned using potable water at a mod
erate pressure (less than 50psi). If the coil cannot be
cleaned using water alone, Lennox recommends
use of a coil cleaner with a pH in the range of 5 to 9.
The coil must be rinsed thoroughly after cleaning.
In coastal areas, the coil should be cleaned with
potable water several times per year to avoid corro
sive buildup (salt).
Indoor Unit (Air Handler or Furnace)
1 - Inspect component wiring for loose, worn or damaged
connections. Confirm proper voltage plus amperage
indoor unit.
2 - Inspect and clean or replace air filters in indoor unit.
3 - Check the cleanliness of indoor blower and clean
blower, if necessary.
4 - Inspect the evaporator coil (Indoor) drain pans and
condensate drains for rust, debris, obstructions, leaks
or cracks. Pour water in pans to confirm proper
drainage from the pan through to the outlet of the pipe.
Clean or replace as necessary.
5 - Inspect and clean evaporator (indoor) coil, if
necessary.
6 - Inspect the condition of the refrigerant lines and
confirm that pipes are not rubbing copper-to-copper.
Also, ensure that refrigerant pipes are not being
affected by indoor air contamination. Check condition
of insulation on the refrigerant lines. Repair, correct, or
replace as necessary.
7 - Inspect the duct system for leaks or other problems.
Repair or replace as necessary.
8 - Check for bearing/bushing wear on indoor blower
motor. Replace as necessary.
9 - Indoor unit inspections of gas- or oil-fired furnaces will
also include inspection and cleaning of the burners,
and a full inspection of the gas valve, heat exchanger
and flue (exhaust) system.
General System Test with System Operating
1 - Your technician should perform a general system test.
He will turn on the air conditioner to check operating
functions such as the startup and shutoff operation.
He will also check for unusual noises or odors, and
measure indoor/outdoor temperatures and system
pressures as needed. He will check the refrigerant
charge per the charging sticker information on the
outdoor unit.
2 - Verify that system total static pressure and airflow
settings are within specific operating parameters.
3 - Verify correct temperature drop across indoor coil.
Page 16