Autonics TCN4H Series Руководство по эксплуатации

Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Контроллер температуры Autonics TCN4H Series. Autonics TCN4H Series 2 страницы. Dual display pid temperature controller
Также для Autonics TCN4H Series: Руководство (2 страниц), Руководство (13 страниц), Руководство по эксплуатации (6 страниц)

Autonics TCN4H Series Руководство по эксплуатации
DRW170776AA
DUAL INDICATOR TEMPERATURE CONTROLLER
TCN4 SERIES
I N S T R U C T I O N M A N U A L
Thank you for choosing our Autonics product.
Please read the following safety considerations before use.
Safety Considerations
※Please observe all safety considerations for safe and proper product operation to avoid hazards.
※Safety considerations are categorized as follows.
Warning Failure to follow these instructions may result in serious injury or death.
Caution Failure to follow these instructions may result in personal injury or product damage.
※The symbols used on the product and instruction manual represent the following
symbol represents caution due to special circumstances in which hazards may occur.
Warning
1. Fail-safe device must be installed when using the unit with machinery that may cause
serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment,
ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster
prevention devices, etc.)
Failure to follow this instruction may result in fire, personal injury, or economic loss.
2. Install on a device panel to use.
Failure to follow this instruction may result in electric shock or fire.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock or fire.
4. Check 'Connections' before wiring.
Failure to follow this instruction may result in fire.
5. Do not disassemble or modify the unit.
Failure to follow this instruction may result in electric shock or fire.
Caution
1. When connecting the power input and relay output, use AWG 20(0.50mm
2
) cable or over and
tighten the terminal screw with a tightening torque of 0.74~0.90N . m.
When connecting the sensor input and communication cable without dedicated cable, use
AWG 28~16 cable and tighten the terminal screw with a tightening torque of 0.74~0.90N . m.
Failure to follow this instruction may result in fire or malfunction due to contact failure.
2. Use the unit within the rated specifications.
Failure to follow this instruction may result in fire or product damage.
3. Use dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in electric shock or fire.
4. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct
sunlight, radiant heat, vibration, impact, or salinity may be present.
Failure to follow this instruction may result in fire or explosion.
5. Keep metal chip, dust, and wire residue from flowing into the unit.
Failure to follow this instruction may result in fire or product damage.
Ordering Information
T
CN
4 S
2 4 R
P
No-mark Bolt wiring method
Wiring method
P
Connector plug connection method
Control output
R
Relay contact + SSR drive output
2
24VAC 50/60Hz, 24-48VDC
Power supply
4
100-240VAC 50/60Hz
Sub output
2
Alarm1 + Alarm2 output
S
DIN W48 × H48mm
M
DIN W72 × H72mm
Size
H
DIN W48 × H96mm
L
DIN W96 × H96mm
Digit
4
9999 (4 digit)
Setting type
CN
Dual display type, set by touch switch
Item
T
Temperature controller
1: Only for TCN4S model.
2: In case of the AC voltage model, SSR drive output method (standard ON/OFF control, cycle
control, phase control) is available to select.
※ The above specifications are subject to change and some models may be discontinued
without notice.
※ Be sure to follow cautions written in the instruction manual and the technical descriptions
(catalog, homepage).
Specification
Series
TCN4S
TCN4M
TCN4H
Power
AC Power
100-240VACᜠ 50/60Hz
supply
AC/DC Power 24VACᜠ 50/60Hz, 24-48VDCᜡ
Allowable voltage range 90 to 110% of rated voltage
AC Power
Max. 5VA(100-240VAC 50/60Hz)
Power
consumption
AC/DC Power Max. 5V(24VAC 50/60Hz), Max. 3W(24-48VDC)
Display method
7 segment (PV: red, SV: green), other display part(green, red) LED method
PV(W×H)
7.0×15.0mm
9.5×20.0mm
7.0×14.6mm
Character
size
SV(W×H)
5.0×9.5mm
7.5×15.0mm
6.0×12.0mm
RTD
DIN Pt100Ω, Cu50Ω (Allowable line resistance max.5Ω per a wire)
Input
type
TC
K(CA), J(IC), L(IC), T(CC), R(PR), S(PR)
Display
RTD
At room temperature(23ºC ± 5ºC): (PV ± 0.5% or ±1ºC, select the higher one) ± 1 digit
accuracy
Out of room temperature range: (PV± 0.5% or ±2ºC, select the higher one)± 1digit
TC
1
For TCN4S- -P, add ±1℃ by accuracy standard.
Control
Relay
250VACᜠ 3A 1a
output
SSR
12VDCᜡ±2V 20mA Max.
Alarm output
AL1, AL2 Relay: 250VACᜠ 1A 1a
Control method
ON/OFF control, P, PI, PD, PID control
1 to 100℃/℉ (0.1 to 50.0℃/℉)
Hysteresis
Proportional band(P)
0.1 to 999.9ºC/℉
Integral time(I)
0 to 9999 sec.
Derivative time(D)
0 to 9999 sec.
Control period(T)
0.5 to 120.0 sec.
Manual reset
0.0 to 100.0%
Sampling period
100ms
AC power
2000VAC 50/60Hz 1min.(between input terminal and power terminal)
Dielectric
strength
AC/DC power 1000VAC 50/60Hz 1min.(between input terminal and power terminal)
Vibration
0.75mm amplitude at frequency of 5 to 55Hz in each X, Y, Z direction for 2 hours
Mechanical OUT: Over 5,000,000 times, AL1/2: Over 5,000,000 times
Relay life
OUT: Over 200,000 times(250VAC 3A resistive load)
cycle
Electrical
AL1/2: Over 300,000 times(250VAC 1A resistive load)
Insulation resistance
Min. 100MΩ(at 500VDC megger)
Noise
Square-wave noise by noise simulator(pulse width 1㎲) ±2KV R-phase and S-phase
Memory retention
Approx. 10 years (when using non-volatile semiconductor memory type)
Ambient temp. -10 to 50ºC, Storage: -20 to 60ºC
Environ
-ment
Ambient humi. 35 to 85%RH, Storage: 35 to 85%RH
Double insulation or reinforced insulation (mark:
Insulation type
the measuring input part and the power part : AC power 2kV, AC/DC power 1kV)
Approval
Approx. 147g
Approx. 203g
Approx. 194g
Weight
2
(approx. 100g)
(approx. 133g)
(approx. 124g)
1:
At room temperature(23ºC±5ºC)
- Below 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±3ºC, select the higher one) ±1 digit
- Over 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±2ºC, select the higher one) ±1 digit
- Termocouple L (IC), RTD Cu50Ω is (PV ±0.5% or ±2ºC, select the higher one) ±1 digit
Out of room temperature range
- Below 200ºC of thermocouple R(PR), S(PR) is (PV ±1.0% or ±6ºC, select the higher one) ±1 digit
- Over 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±5ºC, select the higher one) ±1 digit
- Thermocouple L(IC), RTD Cu50Ω is (PV ±0.5% or ±3ºC, select the higher one) ±1 digit
For TCN4S- -P, add ±1℃ by accuracy standard.
2: The weight includes packaging. The weight in parentheses is for unit only.
Environment resistance is rated at no freezing or condensation.
Unit Description
1. Present temperature (PV) display (Red)
1) RUN mode: Present temperature (PV) display
2) Parameter setting mode: Parameter display
2. Set temperature (SV) display (Green)
1) RUN mode: Set temperature (SV) display
1
2) Parameter setting mode
: Parameter setting value display
3. Control/Alarm output display indicator
8
1) OUT: It turns ON when the control output is ON.
3
During SSR drive output type in CYCLE/
2
PHASE control, this indicator turns ON when
7
MV is over 3.0%.
4
2) AL1/AL2: It turns ON when the alarm output is ON.
5
4. Auto tuning indicator
AT indicator flashes by every 1 sec during operating
auto tuning.
5.
key
6
Used when entering into parameter groups,
returning to RUN mode, moving parameter, and saving
setting values.
6. Adjustment
Used when entering into set value change mode, digit moving and digit up/down.
1
7. Digital input key
2
Press
keys for 3 sec. to operate the set function
(RUN/STOP, alarm output reset, auto tuning) in digital input key [DI-T].
8. Temperature unit (
/℉) indicator
ºC
It shows current temperature unit.
Input Sensor and Temperature Range
Input sensor
Display
Temperature range(
-50 to 1200
KCaH
K(CA)
-50.0 to 999.9
KCaL
JIcH
-30 to 800
J(IC)
JIcL
-30.0 to 800.0
-40 to 800
LIcH
Thermocouple
L(IC)
-40.0 to 800.0
LIcL
TCcH
-50 to 400
T(CC)
TCcL
-50.0 to 400.0
R(PR)
0 to 1700
RPR
S(PR)
0 to 1700
SPR
DPtH
-100 to 400
DPt100Ω
-100.0 to 400.0
DPtL
RTD
-50 to 200
CUsH
Cu50Ω
CUsL
-50.0 to 200.0
Dimensions
TCN4L
TCN4S Series
48
6
64.5
11.0×22.0mm
7.0×14.0mm
TCN4H Series
6
64.5
48
Bracket
TCN4S Series
TCN4M, TCN4H, TCN4L Series
31
48.6
20
5
45
, dielectric strength between
15
21
Approx. 275g
55
(approx. 179g)
56
Connections
1)TCN4S Series
AL1 OUT
SSR
250VAC
OUT
※1
1A 1a
AL2 OUT
250VAC
1A 1a
Relay OUT
B'
250VAC
3A 1a
B
A
RTD
※2
SOURCE
2)TCN4S- -P
SSR
※1
OUT
Relay OUT
250VAC
3A 1a
※2
SOURCE
ºC
) Temperature range(℉)
※ TCN4 Series has selectable control output; Relay output, and
-58 to 2192
SSR drive output. AC/DC voltage type does not have SSRP
-58.0 to 999.9
function.
※1: 12VDC±2V 20mA Max.
-22 to 1472
※2: AC voltage type: 100-240VAC 5VA 50/60Hz
-22.0 to 999.9
AC/DC voltage type: 24VAC 5VA 50/60Hz
-40 to 1472
24-48VDC 3W
(unit: mm)
-40 to 999.9
※Use crimp terminals or teminals of size specified below.
Terminal
a
-58 to 752
a
b
c
number
-58.0 to 752.0
1 to 8
6
Max. 1.7 Max. 3.7
c
b
32 to 3092
9 to 11
6 to 8 Max. 2.1 Max. 4.2
<Crimp terminal>
12 to 14 6 to 8 Max. 1.5 Max. 3.5
32 to 3092
-148 to 752
a b
a b
-148.0 to 752.0
<Round>
<Forked>
-58 to 392
a
Min. 3.0
Min. 3.0
-58.0 to 392.0
b
Max.5.8
Max.5.8
TCN4S- -P
6
56
11.5
48
1.7
TCN4L Series
96
6
64.5
Panel cut-out
A
C
46
Size
A
B
C
D
Series
TCN4S
Min. 65
Min. 65
45
45
0.6
0
TCN4M
Min. 90
Min. 90
68
68
0.7
0
12
TCN4H
Min. 65
Min. 115
45
0.6
92
0
23.9
TCN4L
Min. 115
Min. 115
92
92
0.8
0
Parameter Groups
3)TCN4M Series
1. All Parameter
Please any key among
,
,
,
SV setting
Parameter 1group
AL1 OUT
SSR
250VAC
OUT
※1
1A 1a
AL1 alarm termerature
TC
AL2 OUT
250VAC
1A 1a
AL2 alarm termerature
Relay OUT
B'
250VAC
3A 1a
B
+
TC
A
+
RTD
SOURCE
※2
4)TCN4H/L Series
AL1 OUT
250VAC
1A 1a
AL2 OUT
250VAC
1A 1a
B'
B
TC
A
RTD
AL1 OUT
250VAC
SSR
1A 1a
※1
OUT
AL2 OUT
Press
key over 3 sec in any parameter group, it saves the set value and returns to RUN mode.
250VAC
Relay OUT
1A 1a
(Exception: Press
250VAC
If no key entered for 30 sec., it returns to RUN mode automatically and the set value of parameter
TC
RTD
3A 1a
B'
is not be saved.
Press
key again within 1 sec. after returning to RUN mode, it advances of the first parameter
B
of previous parameter group.
A
Press
key to move next parameter.
Parameter marked in
Set parameter as 'Parameter 2 group → Parameter 1 group → Setting group of set value' order
SOURCE
※2
considering parameter relation of each setting group.
1: It is not displayed for AC/DC power model (TCN4 -22R).
(unit: mm)
TCN4M Series
72
6
64.5
Terminal cover(sold separately)
RSA-COVER(48×48mm)
RMA-COVER(72×72mm)
70
3
48.4
9.8
22.5
RHA-COVER(48×96mm)
RLA-COVER(96×96mm )
47.2
4
94
3
0.6
0
0.7
0
0.8
0
0.8
0
Run mode
2sec.
4sec.
Parameter 2group
PAR1
PAR2
Input
Temperature
Input
Input
sensor
unit
correction
digital filter
AL1
IN-T
UNIT
IN-B
MAvF
AL2
Control output
SV high-
SV low-limit
Control type
operation
limit value
value
Auto tunung
C-MD
O-FT
H-SV
L-SV
AT
Proportional band
SSR drive output
Control output
Control
AL1 alarm
method
※1
P
type
cycle
operation mode
OUT
SSrM
T
AL-1
Integral time
I
LBA detection
LBA
Alarm output
AL2 alarm
band
monitoring time
hysteresis
operation mode
Derivative time
LBaT
AHYS
AL-2
LBaB
D
Manual reset
REST
Digital input
Control output MV in case
Parameter
key
of input break error
lock
DI-K
ErMV
LOC
Hysteresis
HYS
3sec.
3sec.
key once in SV setting group, it returns to RUN mode).
might not be displayed depending on other parameter settings.