Detach the Case or DIP Switch Cover
■ FXM
• Push and pull the groove of DIP switch cover with a flat
head (-) driver to the front, detaching the cover from the
case.
■ FXH
• Push the groove of the front guide with a flat head (-)
driver and pull it to the front.
• Pull the front guide to the front. The case is detached.
DIP switch is located inside.
᜸ Caution: Turn OFF the power before detaching the cover or case.
᜸ Caution: When using the tools, be careful not to be wounded.

DIP Switch Setting

8 7 6 5 4 3 2 1 5 4 3 2 1
ON
OFF
SW1
SW2
■ DIP SW1
Function
SW1
Defaults
Counter
Timer
-
OFF
1
Time range
OFF
2
Input operation
mode
OFF
3
Count up / count down
OFF
4
5, 6, 7 Output operation mode
OFF
01)
OUT1 One-shot output
OFF
8
02)
01)  Except the indicator model.
02) Only for 2-stage setting model.
• [Counter] Input operation mode
SW1
Count up / count down &
input operation mode
4
3
2
Up / Down - A
OFF OFF OFF
(command)
Up / Down - B
OFF OFF ON
Count
(individual)
up
Up / Down - C
OFF ON
OFF
(phase difference)
OFF ON
ON
UP
Up / Down - D
ON
OFF OFF
(command)
Up / Down - E
ON
OFF ON
Count
(individual)
down
Up / Down - F
ON
ON
OFF
(phase difference)
Down
ON
ON
ON
• [Timer] Time range
SW1
Time range
3
2
1
4-digit
6-digit
OFF OFF OFF 99.99 s
99999.9 s
999.9 s
999999 s
OFF OFF ON
OFF 9999 s
99 m 59.99 s
OFF ON
99 m 59 s
999 m 59.9 s
OFF ON
ON
OFF OFF 999.9 m
99999.9 m
ON
99 h 59 m
99 h 59 m 59 s
ON
OFF ON
OFF 999.9 h
9999 h 59 m
ON
ON
9999 h
99999.9 h
ON
ON
ON
• Input logic
SW2-1
Input logic
NPN (no-voltage input)
ON
PNP (voltage input)
OFF
• [Counter] Max. counting speed
SW2
Max. counting speed
3
2
1 cps
OFF
ON
30 cps
OFF
OFF
2 kcps
ON
OFF
5 kcps
ON
ON
• Detach the case or cover of DIP switch
and proceed the settings. See the 'Detach
the Case or DIP Switch Cover.'
• How to change the settings:
power OFF → change settings → power
ON → press [RESET] key or input the
RESET signal (≥ 20 ms) to the external
terminal.
■ DIP SW2
Function
SW2
Defaults
Counter
Timer
CP1, CP2, INHIBIT, RESET
OFF
1
input logic
OFF
2
Max. counting
-
speed
OFF
3
Counter / Timer
ON
4
Memory retention
OFF
5
• Output operation mode
(1-stage / 2-stage setting model)
SW1
Output operation mode
7
6
5
Counter
Timer
OFF OFF OFF F
N
OFF OFF ON
OFF C
OFF ON
R
-
OFF ON
ON
OFF OFF K
ON
P
ON
OFF ON
OFF Q
ON
ON
S
S
ON
ON
ON
• OUT1 One-shot output
(2-stage setting model)
SW1-8
OUT1 One-shot output
One-shot
ON
Hold
OFF
8-digit
999999.99 s
9999999.9 s
99999999 s
99999 m 59.9 s
9999999.9 m
999 h 59 m 59.9 s
9999 h 59 m 59 s
99999 h 59.9 m
• Counter / Timer
SW2-4
Counter / Timer
Counter
ON
Timer
OFF
• Memory retention
SW2-5
Memory retention
×
ON
OFF

Input Connections

• Input: CP1, CP2 (INHIBIT), RESET
• Max. counting speed in the contact input: 1 or 30 cps setting (counter).
■ No-voltage (NPN) input
• Solid-state input
Sensor
(NPN output)
Counter / Timer
Brown
+12 V
5.4 kΩ
Black
Internal circuit
of input part
Blue
0 V
• Contact input
Counter / Timer
+12 V
5.4 kΩ
Internal circuit
of input part
0 V
■ Voltage (PNP) input
• Solid-state input
Sensor
(PNP output)
Counter / Timer
Brown
+12 V
Black
Internal circuit
of input part
10.8 kΩ
Blue
0 V
• Contact input
Counter / Timer
+12 V
Internal circuit
of input part
10.8 kΩ
0 V
Sensor
(NPN open collector output)
Counter / Timer
Brown
+12 V
5.4 kΩ
Black
Internal circuit
of input part
Blue
0 V
Sensor
(PNP open collector output)
Counter / Timer
Brown
+12 V
Black
Internal circuit
of input part
10.8 kΩ
Blue
0 V