Autonics ARIO-C-MR Руководство по эксплуатации - Страница 3

Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Системы ввода/вывода Autonics ARIO-C-MR. Autonics ARIO-C-MR 4 страницы. Slim remote i/o

Unit Descriptions
• It may differ depending on the model.
• Refer to the 'Dimensions' in case of the module.
■ Coupler
4
1
3
2
01. Communication connector
ARIO-C-EC/PN/EI/MT
RJ-45 connectors: 2
02. Communication setting switch
ARIO-C-EC
ARIO-C-CL/DN
Decimal rotary switches: 3
None
(communication speed, address
(×10, ×1))
Cautions during Installation
᜸ Follow the regulations below to configure the modules. For the configuration
of the unit, refer to the figure below.
᜸ For more information, be sure to see the 'Manual of ARIO Series.'
• The number of connected modules: up to 32 or 64 modules
• The length of connection: 768 mm (include the power module and except the coupler/
end modules)
• 8 digital I/O modules and 4 analog/special modules can be connected to ARIO-P-B or
ARIO-P-F1.
• Do not connect the temperature input module at the left and right side of the power
module.
• If you placed the coupler on the left side, recommend installing the modules with a bit
or 1-byte type on the right side of the I/O module with word type.
Coupler
6
01. Communication connector
02. Communication setting switch
03. Setting connector
5
(USB 2.0 type Micro B)
04. Indicators for the power and
communication status
05. Power terminal block
6
06. ABUS communication connector
ARIO-C-PB
ARIO-C-CL/DN/MR
D SUB-9 Pin
5-pin PCB Connector
The others
Hexagonal rotary switches: 2
(address (×16, ×1))
Module
End module
Specifications
■ Coupler
Model
ARIO-C-EC
Protocol
Transfer rate
100 Mbps
Max. connections
≤ 64
for modules
Memory map
1024 Byte
Communication
RJ45 × 2
connector
Setting connector
USB 2.0 type Micro B
Model
ARIO-C-EI
Protocol
Transfer rate
10/100 Mbps
Max. connections
≤ 64
for modules
Memory map
1008 Byte
Communication
RJ45 × 2
connector
Setting connector
USB 2.0 type Micro B
• ABUS (external consump.): 24 VDCᜡ, ≤ 400 mA
(≤ 9.6 W, coupler + module, ≤ 200 mA/CH, 2 CH/COM)
Power supply
• ABUS (internal supply): 5 VDCᜡ, ≤ 960 mA (≤ 4.8 W, module)
• I/O: 24 VDCᜡ, ≤ 4,000 mA (≤ 96 W, ≤ 2,000 mA/CH, 2 CH/COM)
Power
24 VDCᜡ, standby/run: 200 mA, Max. load: 400 mA (coupler max. load)
consumption
■ Module
Type
Digital input
Model
ARIO-S-DI□□
Channel
4 CH, 8 CH model
I/O common
NPN, PNP model
I/O signal level
24 VDCᜡ ± 10 %
Turn ON: ≥ 7 VDCᜡ
Input voltage
Turn OFF: ≤ 0.4 VDCᜡ
Output leakage
-
voltage
I/O current
6 mA/CH
consumption
Rated output
-
current
Power
ABUS: 5 VDCᜡ, ≤ 100 mA (≤ 0.5 W)
consumption
On delay time
≤ 0.5 ms
Off delay time
≤ 1.5 ms
Internal
transmission
4 Mbps
speed
Insulation
I/O to inner circuit: photocoupler insulated
Type
Analog input
Model
ARIO-S-AI□V1
Channel
2 CH, 4 CH model
Input method
Voltage input
Input range
-10 to 10 VDCᜡ
• Room temperature: PV ±0.3% F.S.
Accuracy
• Out of room temperature: PV ±0.6% F.S.
Input impedance
≥ 1 MΩ
Status indicator
≤ -1 V or ≥ 1 V
ON
Resolution
12-bit
• ABUS: 5 VDCᜡ, ≤ 180 mA (≤ 0.9 W)
Power
consumption
• I/O: 24 VDCᜡ, ≤ 15 mA (≤ 0.36 W)
Internal
transmission
4 Mbps
speed
• I/O to inner circuit: photocoupler insulated
Insulation
• Between channels: non-insulated
Type
Analog output
Model
ARIO-S-AO□V1
Channel
2 CH, 4 CH model
Output method
Voltage output
Output range
-10 to 10 VDCᜡ
• Room temperature: PV ±0.3% F.S.
Accuracy
• Out of room temperature: PV ±0.6% F.S.
Load resistance
≥ 5 kΩ
Status indicator
≤ -1 V or ≥ 1 V
ON
Resolution
12-bit
• ABUS: 5 VDCᜡ, ≤ 180 mA ( ≤ 0.9 W)
Power
consumption
• I/O: 24 VDCᜡ, ≤ 15 mA (≤ 0.36 W)
Internal
transmission
4 Mbps
speed
• I/O to inner circuit: photocoupler insulated
Insulation
• Between channels: non-insulated
ARIO-C-CL
ARIO-C-PN
ARIO-C-PB
10 Mbps
100 Mbps
12 Mbps
≤ 32
≤ 64
≤ 32
512 Byte
1024 Byte
488 Byte
5-pin PCB
RJ45 × 2
9-pin D SUB
ARIO-C-DN
ARIO-C-MT
ARIO-C-MR
ModbusTCP
ModbusRTU
compatible
compatible
500 kbps
10/100 Mbps
115.2 kbps
≤ 32
≤ 64
≤ 32
510 Byte
1024 Byte
512 Byte
5-pin PCB
RJ45 × 2
5-pin PCB
Digital output
ARIO-S-DO□□
-
≤ 1.2 VDCᜡ
-
500 mA/CH
ARIO-S-AI□V2
ARIO-S-AI□C1
ARIO-S-AI□C2
Current input
0 to 10 VDCᜡ
0 to 20 mA
4 to 20 mA
≤ 250 Ω
≥ 1 V
≥ 1 mA
≥ 4 mA
ARIO-S-AO□V2
ARIO-S-AO□C1
ARIO-S-AO□C2
Current output
0 to 10 VDCᜡ
0 to 20 mA
4 to 20 mA
≤ 350 Ω
≥ 1 V
≥ 1 mA
Always ON
• ABUS: 5 VDCᜡ, ≤ 100 mA (≤ 0.5 W)
• I/O: 24 VDCᜡ, ≤ 60 mA (≤ 1.44 W)