Autonics ARIO-C-MR Руководство по эксплуатации - Страница 3
Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Системы ввода/вывода Autonics ARIO-C-MR. Autonics ARIO-C-MR 4 страницы. Slim remote i/o
Unit Descriptions
• It may differ depending on the model.
• Refer to the 'Dimensions' in case of the module.
■ Coupler
4
1
3
2
01. Communication connector
ARIO-C-EC/PN/EI/MT
RJ-45 connectors: 2
02. Communication setting switch
ARIO-C-EC
ARIO-C-CL/DN
Decimal rotary switches: 3
None
(communication speed, address
(×10, ×1))
Cautions during Installation
Follow the regulations below to configure the modules. For the configuration
of the unit, refer to the figure below.
For more information, be sure to see the 'Manual of ARIO Series.'
• The number of connected modules: up to 32 or 64 modules
• The length of connection: 768 mm (include the power module and except the coupler/
end modules)
• 8 digital I/O modules and 4 analog/special modules can be connected to ARIO-P-B or
ARIO-P-F1.
• Do not connect the temperature input module at the left and right side of the power
module.
• If you placed the coupler on the left side, recommend installing the modules with a bit
or 1-byte type on the right side of the I/O module with word type.
Coupler
6
01. Communication connector
02. Communication setting switch
03. Setting connector
5
(USB 2.0 type Micro B)
04. Indicators for the power and
communication status
05. Power terminal block
6
06. ABUS communication connector
ARIO-C-PB
ARIO-C-CL/DN/MR
D SUB-9 Pin
5-pin PCB Connector
The others
Hexagonal rotary switches: 2
(address (×16, ×1))
Module
End module
Specifications
■ Coupler
Model
ARIO-C-EC
Protocol
Transfer rate
100 Mbps
Max. connections
≤ 64
for modules
Memory map
1024 Byte
Communication
RJ45 × 2
connector
Setting connector
USB 2.0 type Micro B
Model
ARIO-C-EI
Protocol
Transfer rate
10/100 Mbps
Max. connections
≤ 64
for modules
Memory map
1008 Byte
Communication
RJ45 × 2
connector
Setting connector
USB 2.0 type Micro B
• ABUS (external consump.): 24 VDCᜡ, ≤ 400 mA
(≤ 9.6 W, coupler + module, ≤ 200 mA/CH, 2 CH/COM)
Power supply
• ABUS (internal supply): 5 VDCᜡ, ≤ 960 mA (≤ 4.8 W, module)
• I/O: 24 VDCᜡ, ≤ 4,000 mA (≤ 96 W, ≤ 2,000 mA/CH, 2 CH/COM)
Power
24 VDCᜡ, standby/run: 200 mA, Max. load: 400 mA (coupler max. load)
consumption
■ Module
Type
Digital input
Model
ARIO-S-DI□□
Channel
4 CH, 8 CH model
I/O common
NPN, PNP model
I/O signal level
24 VDCᜡ ± 10 %
Turn ON: ≥ 7 VDCᜡ
Input voltage
Turn OFF: ≤ 0.4 VDCᜡ
Output leakage
-
voltage
I/O current
6 mA/CH
consumption
Rated output
-
current
Power
ABUS: 5 VDCᜡ, ≤ 100 mA (≤ 0.5 W)
consumption
On delay time
≤ 0.5 ms
Off delay time
≤ 1.5 ms
Internal
transmission
4 Mbps
speed
Insulation
I/O to inner circuit: photocoupler insulated
Type
Analog input
Model
ARIO-S-AI□V1
Channel
2 CH, 4 CH model
Input method
Voltage input
Input range
-10 to 10 VDCᜡ
• Room temperature: PV ±0.3% F.S.
Accuracy
• Out of room temperature: PV ±0.6% F.S.
Input impedance
≥ 1 MΩ
Status indicator
≤ -1 V or ≥ 1 V
ON
Resolution
12-bit
• ABUS: 5 VDCᜡ, ≤ 180 mA (≤ 0.9 W)
Power
consumption
• I/O: 24 VDCᜡ, ≤ 15 mA (≤ 0.36 W)
Internal
transmission
4 Mbps
speed
• I/O to inner circuit: photocoupler insulated
Insulation
• Between channels: non-insulated
Type
Analog output
Model
ARIO-S-AO□V1
Channel
2 CH, 4 CH model
Output method
Voltage output
Output range
-10 to 10 VDCᜡ
• Room temperature: PV ±0.3% F.S.
Accuracy
• Out of room temperature: PV ±0.6% F.S.
Load resistance
≥ 5 kΩ
Status indicator
≤ -1 V or ≥ 1 V
ON
Resolution
12-bit
• ABUS: 5 VDCᜡ, ≤ 180 mA ( ≤ 0.9 W)
Power
consumption
• I/O: 24 VDCᜡ, ≤ 15 mA (≤ 0.36 W)
Internal
transmission
4 Mbps
speed
• I/O to inner circuit: photocoupler insulated
Insulation
• Between channels: non-insulated
ARIO-C-CL
ARIO-C-PN
ARIO-C-PB
10 Mbps
100 Mbps
12 Mbps
≤ 32
≤ 64
≤ 32
512 Byte
1024 Byte
488 Byte
5-pin PCB
RJ45 × 2
9-pin D SUB
ARIO-C-DN
ARIO-C-MT
ARIO-C-MR
ModbusTCP
ModbusRTU
compatible
compatible
500 kbps
10/100 Mbps
115.2 kbps
≤ 32
≤ 64
≤ 32
510 Byte
1024 Byte
512 Byte
5-pin PCB
RJ45 × 2
5-pin PCB
Digital output
ARIO-S-DO□□
-
≤ 1.2 VDCᜡ
-
500 mA/CH
ARIO-S-AI□V2
ARIO-S-AI□C1
ARIO-S-AI□C2
Current input
0 to 10 VDCᜡ
0 to 20 mA
4 to 20 mA
≤ 250 Ω
≥ 1 V
≥ 1 mA
≥ 4 mA
ARIO-S-AO□V2
ARIO-S-AO□C1
ARIO-S-AO□C2
Current output
0 to 10 VDCᜡ
0 to 20 mA
4 to 20 mA
≤ 350 Ω
≥ 1 V
≥ 1 mA
Always ON
• ABUS: 5 VDCᜡ, ≤ 100 mA (≤ 0.5 W)