AutoPulse 4100-3113AR Руководство по установке - Страница 8

Просмотреть онлайн или скачать pdf Руководство по установке для Блок управления AutoPulse 4100-3113AR. AutoPulse 4100-3113AR 10 страниц. Idnet 2 sprinkler card and idnet loop card

4100-3113AR IDNet 2 Sprinkler Card, and 4100-3111 IDNet Loop Card Installation Instructions
-
Loop 4 = Jumper P1 on the right IDNet Loop Card
2.
Route the wiring from the primary terminals (B+, B-) to the corresponding inputs on the first device.
Note: When using Class B wiring, you can add up to four circuits for each IDNet loop on the terminal block, see Figure 13.
3.
Route the wiring from the first device to the next as in/out, see Figure 13. Repeat this step for each device.
Class B wiring notes:
• If there are remote isolators or isolator bases on the loops, you must begin addressing the devices on the output and assign each successive
isolator a higher address than the isolator it precedes. For Class B wiring only, the A output and B output of a loop are connected in parallel for
wiring convenience.
• If there are no remote isolators or isolator bases on the loops, you can assign the device addresses in any sequence.
Programming
Adding the sprinkler card using the
Add the sprinkler card to the sprinkler control panel using the Panel Programmer.
To add the sprinkler card using the Panel Programmer, complete the following steps:
1.
Launch the Panel Programmer software.
2.
Create a job, or open an existing job.
3.
Click the Hardware tab.
4.
In the Hardware Configuration area, expand the Unit, Box and Bay configuration where you want to add the card.
5.
In the Available Hardware area, expand the INTERFACE option. Drag the 4100-3113AR IDNet 2 Sprinkler card to the bay in the Hardware
Configuration area.
page 8
Figure 12: Class B jumper setting
Figure 13: IDNet loop Class B wiring
579-1214AR Rev. B