Galletti FM 43 Техническое руководство - Страница 4

Просмотреть онлайн или скачать pdf Техническое руководство для Кондиционер Galletti FM 43. Galletti FM 43 20 страниц. High wall-mounted fan coil units with bldc motor and incorporated valve 2.0 kw-3.7 kw

Galletti FM 43 Техническое руководство
FM
2 CONSTRUCTIVE FEATURES
FAN-DRIVE ASSEMBLY
Tangential fan directly coupled to an electronically controlled electric motor
of synchronous brushless type (BLDC) controlled by inverter.
The great advantage of brushless motors is the significant reduction in power
consumption, which reaches up to a 2/3 of that of asynchronous motors with
the corresponding reduction in CO2 emissions. The DC Inverter technology
allows to continuously adjust the air flow and heating capacity to the actual
needs of the environment by considerably reducing the fluctuations in room
temperature that are typical of step-by-step adjustments.
Temperature pattern with 3-speed motor and brushless motor
3-speed
motor
The direct consequence is the reduction in the noise emission of the fan coil,
which is proportional to the demands of the environment.
Noise pattern with 3-speed motor and brushless motor
CONTROL SYSTEM
The microprocessor control system with infrared user interface enables the
automatic control of the fan coil unit.
The main control specifications are:
-
Selection of the cooling, heating, dehumidification mode or the automatic
mode.
-
PID control algorithm to regulate the BLDC fan: the control logic adapts
the fan rpm to the difference between measured temperature and set
temperature, integrate over time the deviation measured and adapt the
rpm accordingly. The derivative logic analyzes the change speed thus
assuring little variations.
4
3-speed
motor
All copying, even partial, of this manual is strictly forbidden
-
Water temperature reading and definition of minimum working temperatures
-
Auxiliary contacts for signalling of heating or cooling mode
-
Inlet contact for remote on/off operation ( (for instance signalling of room
occupied)
-
Serial port for the implementation of master/slave networks
-
Autorestart after power cut.
REMOTE CONTROL
Infrared remote control with LCD display, to set all the functions of the fan coil:
-
Switching on and off
-
Temperature Set point
-
Operating mode (cooling-dehumidification-ventilation-heating-automatic)
-
Ventilation (automatic-maximum-medium-minimum)
-
Switching on and off via Timer
-
Air outlet flap sweep
-
Clock
When, in a maser/slave system, the fan coil with remote control is the master
unit, the settings are automatically sent to the slave units.
The flap sweep function is not applicable.
AIR FILTER
The filter is washable and can be easily removed for cleaning operations, by
lifting the front panel of the cabinet.

3 ACCESSORIES

available as an option is a wired wallpad with a large display, which can be
used to control and set all the functions of each individual fan coil unit in
master/slave systems.
WALLPAD supplied with cable for the connection to the fan coil unit.
FC66003740 - Rev 01