Agrowtek VX12i Руководство по эксплуатации - Страница 13

Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Контроллер Agrowtek VX12i. Agrowtek VX12i 15 страниц. Digital irrigation valve controller

Agrowtek VX12i Руководство по эксплуатации
Serial Speed & Format
The default serial data format for the LX2 ModLINK interface is: 19,200 baud, 8-N-1.
Alternate speeds and formats between 9,600 - 115,200 baud may be con gured with the free AgrowLINK PC
utility using a LX1 USB AgrowLINK and the cross-over adapter supplied with the LX2 ModLINK.
LX1 USB AgrowLINK™
USB
See MODBUS manual for more information.
MODBUS Manual

Supported Commands

0x01 Read Coils
0x03 Read Multiple Registers
0x05 Write Single Coil
0x06 Write Single Register
0x15 Write Multiple Coils
A request to use a function that is not available will return an illegal function error (0x01).

Register Types

Data registers are 16 bits wide with addresses using the standard MODICON protocol. Floating point values
use the standard IEEE 32-bit format occupying two contiguous 16 bit registers. ASCII values are stored with
two characters (bytes) per register in hexadecimal format. Coil registers are single bit values which control
and indicate the status of a relay; 1 = on, 0 = o .
13
LX2 ModLINK™
GrowNET™
Cross-Over
Cross-Over
7 - 24 Vdc
© Agrowtek Inc. | www.agrowtek.com | Technology to Help You Grow™