Emerson Network Power NetSure 501 A91-S1 Руководство пользователя - Страница 14

Просмотреть онлайн или скачать pdf Руководство пользователя для Источник питания Emerson Network Power NetSure 501 A91-S1. Emerson Network Power NetSure 501 A91-S1 20 страниц. Subrack power system

Emerson Network Power NetSure 501 A91-S1 Руководство пользователя
6
Chapter 2 Installation Instruction
Load route rated
current
100A
63A
32A
16A
10A
Note: The specs are applicable at ambient temperature of 25° C. If the temperature is higher than this, the CSA of the cable should
be increased
To prevent the air switching capacity is too large, the load overload does not work. Recommended the capacity of the
air switching is up to 1.5 ~ 2 times of the load peak.
The CSA of the system grounding cables should be consistent with the largest power distribution cables. The CSA
value is no less than 25mm
AC and DC power distribution interface definition see Table 2-4.
Connector name
AC input MCB
AC power
distribution
Grounding
busbar
Battery output
MCB
DC power
Negative
distribution
output MCB
Positive
busbar

2.3 Mechanical Installation

Note
1. The cabinet or rack the subrack power supply system installed in must provide fireproof and electric protection casing, or
install in cement or other difficult to burn, at the same time and other combustible materials to keep enough distance.
2. For the convenience of maintenance, users should maintain a clearance of 800mm at the front of the power supply system.
3. Subrack cannot be installed against the wall, it must leave enough space for heat dissipation.
Installed on battery bracket
1. Fix the subrack power system to the battery bracket through the connectors with M6 bolts, as shown in Figure 2-1.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Table 2-3 DC load cable selection
Max. output
Min. cable
current
CSA
2
80A
25mm
2
50A
16mm
2
25A
10mm
2
12A
6mm
2
8A
6mm
2
.
Table 2-4 AC and DC power distribution interface definition
H type terminal, max. cable CSA 35mm
H type terminal, max. cable CSA 25mm
One M8 bolt, OT type wiring terminal, max. cable CSA 35mm
H type terminal, max. cable CSA 25mm
H type terminal, max. cable CSA 50mm
H type terminal, max. cable CSA 25mm
H type terminal, max. cable CSA 50mm
Terminal subrack terminal:cable CSA ≤ 50mm
Max. cable length (volt drop:
0.5V, with min. CSA)
14m
9m
11m
14m
23m
Connector specifications
2
(Single-phase power input)
2
(Three -phase power input)
2
(63A and below)
2
(capacity above 63A)
2
(63A and below)
2
(capacity above 63A)
Max. cable length (volt drop:
Max. cable CSA
0.5V, with max. CSA)
2
50mm
2
25mm
2
25mm
2
25mm
2
25mm
AC power line
Connected to the
2
grounding bar of the
equipment room
Connected to the battery
port
Connected to the users load
port
Connected to the users load
2
port
20m
14m
29m
48m
98m
Wiring instructions