BMS Switch
The FAM1 can be integrated with a BMS to make or break a circuit on utility status on/ off. This will
tell the BMS whether or not power is being sent to the utility.
There is a dipswitch located on the circuit board labelled [BMS SEL]. This is factory set to 'OFF'
which signals the BMS on Utility status on/off.
When switched to 'ON', the FAM1 will only signal the BMS on a fault, i.e., emergency stop pressed.
Auto Reset Switch
The FAM1 has an auto reset feature.
There is a dipswitch located on the circuit board labelled [AUTO RESET]. This is factory set to 'OFF'.
When the power is restored after the power loss, the panel has to be restarted manually.
Upon installation, this can be switched to 'ON' - this will instruct the system to restart automatically
when power is restored in the event of a power cut/failure.
Fire Alarm Integration
The FAM1 can be integrated with a fire alarm to close the gas supply automatically in the event of a fire.
The dry contact fire alarm signal can be wired to FAM1 using two-core cable.
Rev: 01
04-23
Installation & Operation Manual
5