Installation & Operation Manual
Switch Settings – Gas Fill & Prove Time
Once the settings have been changed - remove power for 10 seconds.
Amount of time the gas valve opens to fill the gas line on power up or reset.
FILL TIME:
Amount of time the system tests the gas line for leaks on power up or reset.
PROVE TIME:
Fill Time
OFF
5 Seconds (Default)
ON
10 Seconds
Switch Settings – Automatic Shut Down Timer
The system has an auto-shut down feature after a selected time.
There are two switches located on the circuit board labelled [TIME1] & [TIME2].
These can be configured to select the required timeout/ shut-down period.
TIME 1
OFF
ON
OFF
ON
Upon timeout the gas supply will be turned off unless other utilities are configured.
Switch Settings – Utility Shutdown Selection
There are two switches located on the circuit board labelled [ELECTR].
This is factory set to 'Off'.
On installation, it can be switched 'On'. This will instruct the system to also turn off Electrics when
performing auto-shut down/ timeout.
Rev: 13
08-22
Prove Time
OFF
ON
TIME 2
OFF
OFF
ON
ON
30 Seconds (Default)
50 Seconds
Timeout Period
2 Hours (Default)
4 Hours
8 Hours
Disabled
Merlin 1000S+