AGS Merlin 2000S Руководство пользователя - Страница 6

Просмотреть онлайн или скачать pdf Руководство пользователя для Детекторы газа AGS Merlin 2000S. AGS Merlin 2000S 12 страниц. Gas proving and ventilation interlock system
Также для AGS Merlin 2000S: Руководство по установке и эксплуатации (12 страниц), Руководство по установке и эксплуатации (12 страниц)

AGS Merlin 2000S Руководство пользователя
Merlin 2000S
3
Installation & Operation
3.1

System ON and OFF

Turn off all appliances
Turn the Fans On.
Turn the key switch to ON position.
To turn the system off, turn the key switch to OFF position.
3.2

Emergency Shut Off

The emergency shut off button is located on the front of the panel.
There is also a facility for remote shut off buttons to be wired in series on the circuit board.
The emergency shut off button(s) will cut off the gas supply when activated.
To reinstate the system, the emergency shut off button(s) will need to be reset and the panel
restarted.
3.3

BMS integration

The Merlin 2000S can be integrated with a BMS to make or break a circuit on
gas on/gas off, (valve open or valve closed). This will tell the BMS whether or not
110-120VAC is being sent to the solenoid.
There is a dip-switch located on the inside facia of the Merlin 2000S labelled
[BMS SEL].
This is factory set in the OFF position which signals the BMS on gas on/gas off.
When switched to the ON position, the 2000S will only signal the BMS on a fault,
i.e. fan fault, CO2 high level detected, gas detected, EM Stop pressed, etc.
3.4

Fan Switch Integration

There is the facility to connect a Fan Switch (FS1 or FS2 sold separately).
The Fan Switch provides the facility to turn on the fan(s) when the key switch on the Merlin 2000S
is in the on position and turn the power off to the fan(s) when the key switch on the Merlin 2000S
is in the off position.
There is a dip-switch located on the circuit board labelled [EM SEL].
This is factory set in the OFF position which instructs the system to shut down
the fan(s) and gas supply on activation of the Emergency shut off button(s).
Rev: 06
05-19
User Guide
6