7.14 Control module:
The control module (Fig. 8) has been factory pre-set to the following conditions.
Settings as per factory preset:
Set point
Diff pressure
Low pressure
High pressure
Pump run timer
Pump number
CRE setting
Should the parameter need changing follow these steps.
The pump parameters are displayed in the following sequence:
z
Set point (SP),
Differential (DIFF),
Low pressure trip (LPR),
High pressure trip (HPR),
Pump run timer (PRT),
Pump Number (NPM),
Relay setting (CRE),
Number of alarms (NAL1/NAL2),
Hours run (HR1/HE2).
Press and hold the set button for 5-7 seconds. (This gains access to the
z
pump parameters).
Press the up/down arrows to change the selected parameter(s) to the desired
z
value.
After changing the required parameter(s) press the set button twice in quick
z
succession to lock the new value into the controller memory.
It is possible to scroll through all the pump parameter values by simply
z
pressing the set button once after each parameter value has been displayed.
Up/down arrows
allow changes to
pump parameter
values
Fig. 8
SP: 3 bar
DIFF: 0.5 bar
LPR: 0.2 bar
HPR: 4.5 bar
PRT: 180
NPM: 2 (do not tamper)
0
- 14 -
Alarm mute button
Set button enables
access to pump
parameter values
Cont ...