Jafar 2911 Руководство по эксплуатации - Страница 6
Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Блок управления Jafar 2911. Jafar 2911 8 страниц. Flanged gate valves with soft seals
Также для Jafar 2911: Руководство по эксплуатации и техническому обслуживанию (10 страниц)
Protect the rubber parts from compression by keeping the gate valve wedge closure halfway open. Secure the
products against shifting during shipping and handling. Heavy gate valves (DN350 and larger) shall be handled
with dedicated eye bolts; the gate valves from DN65 to DN300 shall be handled on slings (see the example diagram
below) and secured from rotating.
5. INSTALLATION
The flanged gate valves with soft seals can be installed in underground pipelines (except for P/N 2511 and 2502,
the buried installation of which requires a suitable chamber / vault) or overground pipeline installations, both
horizontal and vertical, with any direction of flow of the medium. Do not install the gate valve with the spindle
downward. The listed products are suitable for joining with the flanged ends of pipelines with the size equal to
that of the valve flanges. Note that the completed installation must not expose the valve to bending or tensile stress
from loading with the unsupported pipeline sections, and the valves must be installed aligned with the piping.
Consider proper compensation of the pipeline dimensional changes from temperature and pressure in the
installation. The gate valve is ready for installation as assembled and adjusted by the manufacturer. Any
dismantling of the gate valve components may result in loss of seal.
Before attempting to install the valve, check the technical and commercial documents delivered with the product
to verify that your media and pipeline operating parameters comply with the manufacturer's declaration. Any
change in the operating conditions must be consulted with the manufacturer beforehand.
Before attempting to assemble the valve, remove the main bore plugs, check the inner surfaces of the valve and
thoroughly flush with water, if necessary. Install the gate valve on a base or a support adequate to the size and
weight of the valve, to prevent strain of the piping with the valve. Use suitable piping flanges, gaskets and bolts
for the valve flange ends. The valve and piping flange holes must be aligned. Tighten the connection flange bolts
crosswise to ensure a proper seal pressure. The gate valve location must prevent exposure to freezing of the
medium flowing through the gate valve. Equip the gate valve with a suitable control - an electric drive unit. When
installing a housing, it is necessary to equip the unit with a street box founded on a base slab. When using a spindle
extension, make sure that the weight of the extension is not transferred to the gate valve spindle. To prevent the
load transfer, use holding pieces, mounted to the chamber/vault walls. Spindle extensions over 3000 mm long shall
be attached via Cardan joints. Having completed the installation, perform a pressure test at a maximum test
pressure equal to 1.5 times the nominal pressure.
Caution! If the product has mechanical damage, do not install it in the pipeline.
Caution! When mounting the valve with the electric actuator in the horizontal position, it is absolutely
necessary to use a support or slings in order to relieve the valve, see example below.