Unit Installation
4.5 Installation Clearance Data
(1) When moving the monobloc unit, it is necessary to adopt 2 pieces of long enough rope to hand the unit
from 4 directions. Included angle between the rope when hanging and moving must be 40°below to prevent
center of the unit from moving.
(2) The monobloc unit should be installed on concrete base that is 10cm height.
(3) Requirements on installation space dimension of unit's bodies are shown in following drawing.
(4) The monobloc unit must be lifted by using designated lifting hole. Take care to protect the unit during lift.
To avoid rusting, do not knock the metal parts.
4.6 Electric Wiring
◆ HLR8Pd/Na-K, HLR10Pd/Na-K
2000
>