How to Wire Thermostat
(1) Uncover the front cover of the monobloc unit and open the control box.
(2) Identify the power specification of the thermostat, if it is 230V , find terminal block XT3 as NO.21~25;
Otherwise, if it is 24V, find terminal block XT3 as NO.26~30;
(3) If it is the heating/cooling thermostat, please connect wire as per the figure above;
CAUTION!
Never use 230V AC and 24V AC thermostat at the same time, otherwise, it will cause short circuit and
①
power cut-off by the circuit breaker;
Setting temperature by the thermostat(heating or cooling) should be within the temperature range of the
②
product ;
For other constrains, please refer to previous pages about the remote air temperature sensor;
③
Do not connect external electric loads. Wire 220V AC(24V AC) and 220V GND(24V GND) should be
④
used only for the electric thermostat.
Never connect external electric loads such as valves, fan coil units, etc. If connected, the mainboard of
⑤
the unit can be seriously damaged.
Installation of the thermostat is very similar to that of the remote air temperature sensor.
⑥
4.14 Wiring of the Control
Notes:
The wired controller can be connected to the terminal of AP1 CN6 or AP2 CN 8 through the four-wire
①
communication line.
AP1 (CN 5) and AP2 (CN 7) have been connected with the communication line (three-wire communication
②
line before delivery.
The remote monitoring device can be connected to the CN4 of the wired controller through a four-wire
③
communication line.
21
22
23
24
Thermostat
Control Box
AP1
CN5
CN6
CN7
CN8
AP2
25
26
27
Thermostat
Long-distance
Minitor PC
CN5
CN4
Wired controller