2 LOCATION - GENERAL
2.11 Access: For emergencies and maintenance the pump must be
2.12 Protection: The pump must be located in a dry position, frost free
2.13 Ventilation: Ensure an adequate air flow to cool the pump. Separate
2.14 Safety: The motor casing can become very hot under normal
2.15 Water retention: Site the pump in a location where in the unlikely
2.16 Static inlet pressure: Before deciding where to locate the unit check to ensure
the static inlet head between pump and the bottom of the cold water tank (Fig. 4)
is at least 0.5 metre and does not exceed the max inlet head of 10 metres.
2.17 Ambient temperature: The pump must be sited in a location where the
maximum ambient temperature does not exceed 40
2.18 Pipework: For optimum performance in new installations pipework must be
22 mm, reducing to 15 mm only when entering the terminal fitting.
If installing in an existing installation 15 mm pipework may be used but will
reduce the pumps performance.
2.19 Static outlet pressure: The static outlet head (Fig. 4) must also be within the
maximum requirement of 10 metres.
2.20 Noise: The anti-vibration mounting feet and flexible hoses which are supplied
as standard, and a precaution to reduce noise transmission, however care must
be taken when mounting the pump that any noise is not amplified through loose
panels or pipework. Do not screw down the pump.
2.21 Direction of flow: Ensure the water inlet supply is
connected to the correct pump ports indicated by
INLET arrow/s detailed on the pump rating label
Fig. 2.
2.22 Flexible hoses: Only use the Bristan hose set supplied with the pump.
2.23 Isolating valves: Separate system isolating valves (full bore) must be fitted to
allow easy pump service (not supplied).
easily accessible.
and protected from freezing, particularly when installed in a loft (not
recommended).
the pump from other appliances that generate heat. An 80 mm (3 ")
air gap must be maintained around the pump.
operating conditions. Care must be taken to ensure it cannot be
touched during operation.
event of a water leak, any spillage is contained or routed to avoid
electrics or areas sensitive to water damage.