Function test
1.
2.
3.
7
Operation
RG 210 automates the control of pumps and valves. The operation
of the RG210 is limited to its regular monitoring:
•
•
8
Maintenance
8.1
Maintenance intervals
Table 4: Maintenance intervals
When
Once per
year
At regular
intervals
RG 210
The connected PTC thermistor(s) are heated up after approx.
8 seconds, provided they are not submerged in liquid.
Perfom a function test, refer to chapter 6.5, page 17.
Submerge the probe(s) in liquid.
The yellow LEDs must light up immediately.
Remove probe(s) from the liquid.
After approx. 8-15 seconds the yellow LEDs must change the
switching state.
Observe the green LED and the relay.
The function sequence must correspond to the description of the
selected operating mode in chapter 3.1, page 7.
Function check OK.
Probe free from deposits.
Activity
Perfom an operation test.
Check the probe(s) for deposits.
There must be no deposits on the glass housing
of the PTC thermistor. If the PTC thermistor is pol-
luted, replace
Perform suitable checks to ensure that the level
switch and its environment are always clean, ac-
cessible and easy to oversee.
probe(s).