SYMPTOMS
NO AIR
MINIMUM AIR
AIR IS NOT HITTING
FLOOR
UNEVEN AIR
EXCESSIVE AIR
MOVEMENT AT
DOORWAY
NO HEAT
MINIMAL HEAT
EXCESSIVE HEAT
EXCESSIVE HEAT
MINIMAL HEAT
X. TROUBLESHOOTING
CAUSE
• Power supply line open (no power)
• Fuse blown/circuit breaker tripped
• Motor overload tripped
• Failed switch
MOTOR RUNNING/FANS ARE NOT ROTATING
• Broken or damaged flexible hub
• Shaft rotating inside fan
ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN
• Selector switch is in off position
• Door limit switch not operating
• Air directional discharge vanes mis-adjusted
• Inadequate intake clearance
• Blower motor operates below speed
• Fan rubbing against housing
• Fan wheels clogged with dirt
• Fan in backwards
• Air stream too weak
• Air stream hits obstruction
• Negative pressure
• Shaft rotating inside fan
• One motor not operating
• Nozzle not angled out far enough
• Unit too powerful
• Air movement too cold
• Pushing air outside building
SEE AIR IS NOT HITTING FLOOR SYMPTOMS
ELECTRICALLY HEATED MODELS
• Switch turned to "ON" position
• Thermostat not set properly
• Coils burned out due to lack of air
• Automatic reset thermal cutout failed in open
position
• Manual reset thermal cutout tripped
(if supplied)
• Thermostat in wrong location - thermostat
too close to discharge
• Improper voltage
• Thermostat not set properly
• Low entering air temperature
• Incorrect speed range
• Thermostat in wrong location
• Thermostat not set properly
• Insufficient air over coil
• Improper voltage
HOT WATER HEATED UNITS
• Too high hot water pressure
• Inadequate air flow, fins plugged up, dirty coils
• Water temperature too low
• Intake air below design temperature
• Check power source, check service disconnect,
check method of control in ON position
• Replace fuse(s)/reset breaker
• Internally protected motor - should reset
automatically after cool-down, if not, replace motor.
• Replace switch
• Replace fan sleeve/reengage coupling
• Tighten set screws/tighten fan on shaft
• Turn switch to "ON" position
• Repair or replace limit switch
• Adjust vanes to proper position, see instructions
• Move air curtain or remove obstruction
Provide adequate space for air curtain
• Improper voltage
• Free fan from housing
• Clean and vacuum fan wheels
• Check fans for blade curve toward discharge
• Adjust nozzle to proper position, adjust motor
speed; see installation instructions
• Remove obstruction or reposition air curtain
(move out 3/8" for every 1" up from the door)
• Relieve negative pressure by providing makeup
air
• Tighten set screws
• Repair or replace motor
• Adjust nozzle angle to outside
• Adjust motor speed
• Add auxiliary heat to overcome wind chill factor
• Adjust discharge angle back into building, adjust
motor speed
• Replace switch or check wiring
• Change thermostat setting
• Correct airflow problem; replace coils
• Replace automatic thermal cutout
• Reset manual thermal cutout
• Move thermostat away from air stream
• Supply proper voltage
• Change temperature setting
• Based on unit temperature rise, reduce speed
• Check Factory Menu speed range matches diagram
• Move the thermostat closer to air stream
• Change temperature setting
• Remove restriction on intake
• Supply proper voltage
• Reduce hot water flow
• Clean intake and coils
• Increase water flow
• Increase water flow
-14-
REMEDY