Fujitsu UTZ-PX1NBA Руководство по установке

Просмотреть онлайн или скачать pdf Руководство по установке для Кондиционер Fujitsu UTZ-PX1NBA. Fujitsu UTZ-PX1NBA 8 страниц. Optional parts, drain pump unit

Fujitsu UTZ-PX1NBA Руководство по установке
AIR CONDITIONER
OPTIONAL PARTS
DRAIN PUMP UNIT
INSTALLATION MANUAL
For authorized service personnel only.
UTZ-PX1NBA
Contents
1. SAFETY PRECAUTIONS .............................................. 1
2. MAIN UNIT AND ACCESSORIES .................................. 1
3. DIMENSION ................................................................... 2
4. LOCATION ..................................................................... 2
5. INSTALLATION PROCEDURES .................................... 3
6. DRAINAGE CONSTRUCTION ...................................... 4
7. ELECTRICAL WIRING ................................................... 5
8. TEST RUNNING ............................................................ 7
9. INSULATION OPERATION ............................................ 8
10. MAINTENANCE DURING OFF SEASON ...................... 8

1. SAFETY PRECAUTIONS

This mark indicates procedures which, if
improperly performed, are most likely to
DANGER
result in the death of or serious injury to the
user or service personnel.
Never touch electrical components immediately after the
power supply has been turned off. Electrical shock may oc-
cur. After turning off the power, always wait 5 minutes or more
before touching electrical components.
This mark indicates procedures which, if
improperly performed, might lead to the
WARNING
death or serious injury of the user.
For the air conditioner to operate satisfactorily, install as outlined
in this installation manual.
Connect the indoor unit and drain pump unit with the air
conditioner hose and cords available standards parts. This
installation manual describes the correct connections using
the installation set available from our standard parts.
Installation work must be performed in accordance with national
wiring standards by authorized personnel only.
Do not turn on the power until all installation work is com-
plete.
This mark indicates procedures which, if
improperly performed, might possibly result
CAUTION
in personal harm to the user, or damage to
property.
Install a drain pump unit to each indoor unit. If 1 drain pump unit
is connected to multiple indoor units, leakage may occur.
Do not exert excess pressure, for example when holding the
supplied drain hose. Otherwise the drain hose may come off
and cause injuries.
Do not turn off the power supply for 5 minutes after the opera-
tion has been stopped. Otherwise the remaining drain water
may not be drained and leakage may occur.
If leakage occurs from the interior of the indoor unit or drain
pump unit during operation of the air-conditioner, stop the
operation immediately. The drain outlet may be jammed and
the safety circuit may not be working properly. Please contact
your dealer.

2. MAIN UNIT AND ACCESSORIES

• The following installation parts are furnished. Use them as
required.
* The parts numbers are the same as those indicated in the
diagrams.
Name and shape
Q'ty
Drain pump unit
1
Installation manual
1
1 Hanger
1
PART NO. 9378754027-04
Name and shape
8 Hose band (Big)
9 Joint hose
0 Special nut A
(Large fl ange)
A Special nut B
(Small fl ange)
Q'ty
1
1
1
1
En-1