Chapter 1
ETERNUS DX Installation
1.7
Outlet/Socket Specifications
AC200V Power Cords (for the EMEIA, North American, Central American, and Caribbean Re-
gions)
AC200V power cords are used to connect devices to the IEC60320 C13 power socket type. These power cords
can be used if the specifications of the connection device allow AC200V.
Table 1.4 Specifications for AC200V Power Cords (for the EMEIA, North American, Central American, and Caribbean
Regions)
Usage
Used for connection be-
tween the ETERNUS DX
and the socket
(IEC60320 C13 n
IEC60320 C14G)
AC200V Power Cords (for Regions other than the EMEIA, North American, Central American,
and Caribbean Regions)
AC200V power cords are used to connect devices to the NEMA L6-15R power socket type. These power cords
can be used if the specifications of the connection device allow AC200V.
Table 1.5 Specifications for AC200V Power Cords (for Regions other than the EMEIA, North American, Central Ameri-

can, and Caribbean Regions)

Usage
Used for connection be-
tween the ETERNUS DX
and the socket
(IEC60320 C13 n NEMA
L6-15P)
AC125V Power Cords (for Regions other than the EMEIA, North American, Central American,
and Caribbean Regions)
AC125V power cords are used to connect devices to the NEMA 5-15R power socket type. These power cords
can be used if the specifications of the connection device allow AC100V.
Table 1.6 Specifications for AC125V Power Cords (for Regions other than the EMEIA, North American, Central Ameri-
can, and Caribbean Regions)
Usage
Used for connection be-
tween the ETERNUS DX
and the socket
(IEC60320 C13 n NEMA
5-15P)
Socket type
Plug type
(Socket)
IEC60320 C14G
IEC60320 C13
Socket type
Plug type
(Socket)
NEMA L6-15P
NEMA L6-15R
Socket type
Plug type
(Socket)
NEMA 5-15P
NEMA 5-15R
FUJITSU Storage ETERNUS DX60 S3 Disk storage system Site Planning Guide
Copyright 2015 FUJITSU LIMITED
Cable length
1.5m
Cable length
4.0m
Cable length
3.0m
22
Voltage rating/current
rating
250V 10A
Voltage rating/current
rating
Rating: 250V 10A
(Normal usage rating:
8A)
Voltage rating/current
rating
Rating: 125V 13A
(Normal usage rating:
10A)
P3AM-8982-03ENZ0