Kohler 4EF Операция - Страница 25

Просмотреть онлайн или скачать pdf Операция для Двигатель Kohler 4EF. Kohler 4EF 48 страниц. Marine generator sets

Kohler 4EF Операция

3.5 Backfire Flame Arrestor

At the interval specified in the service schedule, inspect,
clean, or replace the backfire flame arrestor. Clean the
arrestor more frequently if the generator set operates in
dirty, dusty conditions. Check the mesh element for
accumulated oil or dirt that could clog the element and
cause poor performance. See Section 1 for location.
Replace a damaged flame arrestor.
USCG-approved Kohler replacement parts. Follow the
procedure described below.
Backfire Flame Arrestor Cleaning Procedure
1. Loosen the hose clamp at the breather hose at the
air silencer fitting and remove the hose.
2. Loosen the hose clamp attaching the air silencer
assembly to the carburetor.
3. Lift off the air silencer assembly.
4. Clean the assembly in evaporative solvent and
wipe clean. Allow to dry.
5. Reassemble using the reverse sequence.
TP-5985 10/02

3.6 Exhaust System

Use only
Inspecting the exhaust system. Carbon monoxide can
cause severe nausea, fainting, or death. For the safety of
the craft's occupants, install a carbon monoxide detector.
Consult the boat builder or dealer for approved detector
location and installation. Inspect the detector before each
generator set use. In addition to routine exhaust system
inspection, test the carbon monoxide detector per the
manufacturer's instructions and keep the detector operational
at all times.
At the interval specified in the service schedule, inspect
the exhaust system components (exhaust manifold,
mixing elbow, exhaust line, hose clamps, silencer, and
outlet flapper) for cracks, leaks, and corrosion.
Exhaust System Inspection Points
Check for exhaust leaks and blockages. Check the
silencer and piping condition and check for tight exhaust
system connections.
D
Check the hoses for softness, cracks, leaks, or dents.
Replace the hoses as needed.
D
Check for corroded or broken metal parts and replace
them as needed.
D
Check for loose, corroded, or missing clamps.
Tighten or replace the hose clamps and/or hangers
as needed.
D
Check that the exhaust outlet is unobstructed.
D
Visually inspect for exhaust leaks (blowby). Check
for carbon or soot residue on exhaust components.
Carbon and soot residue indicates an exhaust leak.
Seal leaks as needed.
D
Ensure that the carbon monoxide detector is (1) in the
craft, (2) functional, and (3) energized whenever the
generator set operates.
WARNING
Carbon monoxide.
Can
cause
severe
fainting, or death.
The
exhaust
system
leakproof and routinely inspected.
Section 3 Scheduled Maintenance
nausea,
must
be
13