2.4.2

Local Operation

Starting. Move the generator set master switch to the
RUN position. The ADC 2100 attempts to start the
generator set three times. If the generator set does not
start in three attempts, the system shuts down on an
overcrank fault.
The crank cycle time is preprogrammed and not
adjustable.
Stopping. Run the generator set with no load for at
least 2 minutes to allow the engine to cool down. Move
the generator set master switch to the OFF/RESET
position. The engine stops.
2.4.3

Automatic Operation

The generator set can be connected to an automatic
transfer switch (ATS), remote start/stop switch or
remote digital gauge. Move the generator set master
switch to the AUTO position to allow starting and
stopping by one of these devices.
Refer to the instructions provided with the ATS, remote
start/stop switch or remote digital gauge for operation
instructions.
Note: Have an authorized Kohler distributor/dealer
install and connect the ATS, remote start/stop
switch, or remote digital gauge.
Automatic Starting. The generator set crank cycle
starts when the remote switch or engine start contacts
on the ATS close. The ADC 2100 attempts to start the
generator set three times. If the generator set does not
start in three attempts, the system shuts down on an
overcrank fault.
Code Fault
HB
High battery
voltage warning
LB
Low battery
voltage warning
Figure 2-3 ADC 2100 Fault Warning Codes
TP-6344 4/09
Description
Fault code is displayed if the engine starting battery voltage rises
above 16 VDC for a 12 VDC system or above 30 VDC for a 24 VDC
system for more than 10 seconds when the engine is not running.
This fault condition does not inhibit engine starting.
The fault condition clears when the battery voltage returns to a voltage
within the limits for more than 10 seconds.
Fault code is displayed if the engine starting battery voltage falls below
9.5 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system
for more than 10 seconds when the engine is not running. This fault
condition does not inhibit engine starting.
The fault condition clears when the battery voltage returns to a voltage
within the limits for more than 10 seconds.
The crank cycle time is preprogrammed and not
adjustable.
Automatic Stopping. With the generator set master
switch in the AUTO position, the generator set stops
when the remote start/stop switch contacts or engine
start contacts on the ATS open.
2.4.4

Fault Warnings and Shutdowns

Warnings. The controller displays a fault code but the
generator set does not shut down under the high battery
voltage (HB) and low battery voltage (LB) warning
conditions shown in Figure 2-3. The controller resets
automatically after a battery voltage fault condition is
corrected.
Shutdowns.
The generator set shuts down
automatically under the conditions listed in Figure 2-4
and the controller displays a fault code. Correct the fault
condition and then reset the controller before restarting
the generator set.
See Section 2.4.5 to reset the
controller after a fault shutdown.
Shutdown switches on the generator set automatically
reset when the problem is corrected. For example, the
high engine temperature switch on the generator set
engine automatically resets when the generator set
cools. However, the fault on the controller does not clear
until the operator resets the controller.
LOP Shutdown. The oil pressure switch shuts down
the generator set if the oil pressure drops below a preset
level, providing some protection from major engine
damage due to insufficient oil pressure. However, the
low oil pressure switch is not a low oil level indicator.
Check the oil regularly as described in the service
schedule and add oil as required to keep the oil level at
or near the full mark on the dipstick or optional gauge.
Check
Check the battery rating
and condition.
Check the battery rating
and condition.
Charge or replace the
battery.
Section 2 Operation