AQmatic NX48 Руководство по эксплуатации - Страница 7

Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Контроллер AQmatic NX48. AQmatic NX48 18 страниц. Nxt stager controller

AQmatic NX48 Руководство по эксплуатации
MASTER PROGRAMMING MODE FLOW
CHART
Before entering Master Programming, please
CAUTION
contact your local professional water dealer.
When the Master Programming Mode is entered, parameters
can be set to make the timer(s) function as needed.
NOTE: Depending on current option settings, some
displays cannot be viewed or set.
Entering Master Programming Mode
1. Press and hold the Shift and Up buttons for 5 seconds.
OR
2. Set the time of day display to 12:01 PM or 12:01HR. Press
and hold Up or Down buttons to set the time. Then press
the Up and Down buttons at the same time for 5 seconds.
Exiting Master Programming Mode
1. Press the Extra Cycle button once per display until all
are viewed. Master Programming Mode is exited and the
normal display screen appears.
2. To exit the Master Programming Mode without saving
changes, press the Diagnostic button.
NOTE: If no keypad activity is made for 5 minutes while
in the Master Programming Mode, or if there is a
power failure, no changes will be saved, and the
unit will go back to the main display screen.
Resets
Soft Reset: Press and hold the Up and Down buttons for 25
seconds until 12:00PM (or 12:00HR) appears. This resets all
parameters except for the
Master Reset: Hold the Extra Cycle button while powering up
the unit. This resets all of the parameters in the unit. Check
and verify the choices selected in Master Programming Mode.
Example:
SELECT LANGUAGE:
English
ENGLISH
Options: English
Espanol
Portugues
Deutsch
Francais
Example:
SYSTEM TYPE:
4
System Type 4, Single Unit
SINGLE UNIT
Options: System 4 (single unit)
System 5 (2-4 units) - Parallel Interlock
System 6 (2-4 units) - Parallel Series Regeneration
System 7 (2 units) - Alternating
System 9 (2-4 units) - Alternating
System 14 (2-4 units) - Demand Recall
Example:
VALVE ADDRESS:
Valve Address #2 (Second Control Valve) (Default)
#2
Options: Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve) (Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
NOTE: This screen will not display for System Type 4.
Example:
SYSTEM SIZE:
2 Valves in the System (Default)
2 VALVES
Options: 2 Valves in the System (Default)
3 Valves in the System
4 Valves in the System
Range: 2 to 4 Valves in the System
Example:
REGEN TYPE:
NOTE: This screen will not display for System Type 4.
Time Clock Delayed (Default)
TIME CLK DELAYED
meter totalizer volume.
Range: 2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
Example:
REGEN TYPE:
Time Clock Delayed (Default)
TIME CLK DELAYED
Options: Time Clock Delayed (System 4 Only) (Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
Example:
VALVE TYPE:
Stager - Notch Cam (Default)
STAGER-NOTCH CAM
Options: 2750
2850
2900
3150
3900
Stager - Notch Cam (Default)
Example:
REMOTE SIGNAL
Off (Default)
START:OFF
Options: 00:06:00 (Hours:Munutes:Seconds)
Range: 1 second to 99 minutes (1 hour, 39 minutes)
NOTE: This display will not be viewed in System 14.
Example:
DISPLAY FORMAT:
U.S. Gallons (Default)
US-GALLONS
Options: U.S. - Gallons (Default)
EU-Metric - Liters (Metric)
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
Example:
UNIT CAPACITY:
0300000 Grains (Default)
0300000 GRAINS
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
1.0 to 190,000 grams CaCO
Capacity in Metric Format
3
NOTE: Use the Shift button to move to the left.
Example:
CAPACITY SAFETY
00% (Default)
FACTOR:
00%
Range: 0 to 50%
NOTE: Use the Shift button to move to the left.
Example:
FEED WATER
HARDNESS: 15 GPG
15 GPG (U.S. Format) (Default)
Range: 1 to 199 Grains/Gallon (U.S. Format)
2 to 199 miligrams CaCO
/L (Metric Format)
s
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
TRIP POINT 1:
000 gpm
1 to 997 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. Use the Shift button to change each
decimal position.
NOTE: This screen will only display for System 14.
TRIP DELAY 1:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. Use the Shift button to move one space
to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 2:
gpm
NXT Stager Controller
2 to 998 gpm
AU11