a-TroniX 9885163 Руководство пользователя - Страница 11

Просмотреть онлайн или скачать pdf Руководство пользователя для ИБП a-TroniX 9885163. a-TroniX 9885163 14 страниц.

User Manual
Extended Battery Pack 6kVA, 10kVA

3.4. Installing the optional battery cabinet

1. Figure 3 shows the connection between the UPS and the battery cabinet.
CAUTION:
A small amount of arcing may occur when connecting an EBP to the UPS.
This is normal and will not harm personnel. Insert the EBP cable into the UPS
battery connector quickly and firmly.
2. Plug the EBP cable(s) into the battery connector(s) as shown in figure 2.
Up to four EBPs may be connected to the UPS.
3. Verify that the EBP connections are tight and adequate bend radius and
strain relief exist for each cable.
Figure 3
Connecting the EBPS:
Set the UPS for the number of battery packs installed.
09/2021
figure 3
Page 11