CP Electronics EBDSPIR Руководство по эксплуатации - Страница 2

Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Датчики безопасности CP Electronics EBDSPIR. CP Electronics EBDSPIR 2 страницы. Ceiling presence detector
Также для CP Electronics EBDSPIR: Руководство по установке (16 страниц), Руководство по эксплуатации (4 страниц)

CP Electronics EBDSPIR Руководство по эксплуатации
1
FLUSH FIXING
Warning - be careful bending
springs when mounting unit.
1
SURFACE FIXING
50mm or 60mm fixing centres
Installation
Installation
The detector should be sited so that the occupants of the room fall
The detector should be sited so that the occupants of the room fall
inside the detection pattern shown overleaf, at a recommended height of
inside the detection pattern shown overleaf, at a recommended height of
2.8m on the ceiling. Note that the lower the sensor is installed the
2.8m on the ceiling. Note that the lower the sensor is installed the
smaller the detection range will be, subject to the parameters shown on
smaller the detection range will be, subject to the parameters shown on
the diagram.
the diagram.
Avoid direct sunlight entering the sensor.
Avoid direct sunlight entering the sensor.
Do not site within 1m of forced air heating
Do not site within 1m of forced air heating
or ventilation.
or ventilation.
Do not site within 1m of any lighting.
Do not site within 1m of any lighting.
Do not fix to a vibrating surface.
Do not fix to a vibrating surface.
Wire the product using the connector using the diagram on the front
Wire the product using the connector using the diagram on the front
page.
page.
Mount using one of the two options above.
Mount using one of the two options above.
2
Hole Ø64mm
2
Pull out spring tab and rotate
spring arm as shown
For lux enabled products, set the LUX level to maximum and the time to
For lux enabled products, set the LUX level to maximum and the time to
minimum.
minimum.
Power the unit up—the load should come on immediately.
Power the unit up—the load should come on immediately.
Vacate the room or remain very still and wait for the load to switch off
Vacate the room or remain very still and wait for the load to switch off
(should take no more than 2 minutes).
(should take no more than 2 minutes).
Check that the load switches on when movement is detected.
Check that the load switches on when movement is detected.
To set the final LUX level wait until the level of natural daylight is just
To set the final LUX level wait until the level of natural daylight is just
enough that lighting is required. Starting with the LUX control fully clock-
enough that lighting is required. Starting with the LUX control fully clock-
wise (at minimum), very slowly turn the control anti-clockwise until the
wise (at minimum), very slowly turn the control anti-clockwise until the
lights come on. Note that when the LUX control is at maximum then the
lights come on. Note that when the LUX control is at maximum then the
lights will always come on with occupancy.
lights will always come on with occupancy.
Set the time required.
Set the time required.
3
4
3
4
5
5
6
LOAD DOES NOT COME ON
LIGHTS DO NOT GO OFF
Ensure that the area is left unoccu-
Check to see if the live supply to
pied for longer than the selected
the circuit is good.
timer setting.
If the supply and wiring are good,
for lux enabled versions, check
Make sure that the sensor is not
the LUX level setting. Increase the
adjacent to circulating air, heaters
LUX level setting to allow the
or lamps.
controller to turn on at higher
ambient natural light level.
If the detection range is smaller
than expected, check the diagram
above. Rotating the sensor slightly
may improve the range.
Fault Finding