CPC 203-5771 Инструкции по установке
Просмотреть онлайн или скачать pdf Инструкции по установке для Аксессуары CPC 203-5771. CPC 203-5771 2 страницы. Duct-mounted humidity sensor
TECHNICAL BULLETIN
Part #: 026-4807 Revision 0 Date: 02/26/2003
Duct-Mounted Humidity Sensor (P/N 203-5771)
CPC specs a duct-mounted relative humidity (RH) sensor with a 0-5VDC output for use in build-
ing control and anti-sweat control applications using CPC input boards.
Specifications
Sensing Element
Digitally profiled thin-film capacitive
Accuracy
±2% RH over the range 20%-90% RH
Stability
±1%@ 20°C (68°F) annually for 2 years
Operating
0-100% RH
Humidity Range
Temperature
±0.03% RH /°C over 0-60°C (32-140°F)
Coefficient
Choosing a Mounting Location
Select a supply air duct that draws air from the area in which you wish to measure relative humid-
ity. You may mount the sensor in any orientation provided the sensor element is in the air stream.
Mounting
1.
Cut a small circular hole in the duct large
enough for the sensor tube to fit through.
2.
Bolt the sensor enclosure against the outside of
the duct wall so that the sensor element fits
through the hole and into the duct. The enclo-
sure may be mounted horizontally (as shown in
Figure 1) or vertically. The screws should be
tight enough for the foam gasket around the
bottom of the sensor to form an airtight seal
between the hole in the duct wall and the out-
side air.
COMPUTER PROCESS CONTROLS - http://www.cpcus.com/
Installation Instructions
Figure 1 - Humidity Sensor - Exploded View
Analog Output
0-5VDC; 3-wire, observe polarity
Scaling
0-100% RH
Input Power
12VDC
EMC
EN 50081-1, EN 50082-1, EN 61000-4-4,
EN 61000-4-5, EN 61000-4-3, ENV
Conformance
50204, EN 61000-4-6
Page 1