VACUUM HOLD TEST
Current Vacuum
Level
Leak test
duration
B) Continue to Evacuate the system to the desired level which is indicated in the
upper left display once the desired vacuum level is reached:
a. On the MD100, close the vacuum valve
b. On the MD50, close the High and Low side valves.
C) Press [SET] to start test. Starting test vacuum level is indicated in upper left
display
display and timer is shown in lower left. The timer decrements and when zero, a
bells sounds and test ends. At end of test, Start vs. Final Vacuum levels will be
displayed to enable determination of any vacuum loss over a set period of time.
Desired Test
Level
Timer counts
backwards
D) Press [CLR] to return to Main Screen (FIG.1].
NOTE: If it is required to rerun the vacuum pump after STEP 3, disconnect and reconnect the
MOXVG to reset it in the vacrometer mode.
PROGRAMMING/SETTING UNITS
According to your geographic location, MD50 and MD100 manifold series are factory
programmed with 5 common refrigerants in those regions (see chart below), and units
of measure (Temperature, Pressure and Vacuum) for specific regions.
Any of these units can be changed via the Program Mode.
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
hh:mm
,nun
cu-t u
Psig
n 5 . n n
U lJU
hh:mm
Vacuum Display Screen
[FIG.18].
Current system vacuum level is shown in upper right of
◄-:
0390
m35
mic
ur
Vacuum Display Screen
TestEquipmentDepot.com
APO
mlc
Vac
Inactive
Current System
Vacuum Level
chart below for details.
See
11