Problems
Signals
Possible causes
PRESFLO
®
No power
will not turn on
PRESFLO
start-up pressure (Pm) for the chosen
application.
Faulty electrical connections or
pump out of service
PRESFLO
PRESFLO
due to "DRY RUNNING" due to lack
of water
The pump will
not start when
Maximum pump pressure is
a tap is turned on
insuf cient
PRESFLO
due to "FREQUENT START-UP"
PRESFLO
RENT"
Filters or pipes may be partly blocked Check the water pipes
The pump
delivers no or low
PRESFLO
pressure
completely
The pump stops
Leaks within the system (less than
and starts
the shut-off ow rate Qa)
repeatedly
The ow rate is higher than the
shut-off ow rate (Qa)
The pump will
not stop
PRESFLO
close or is damaged
= Off
= On
= Flashing
Exploded view of
1 - Circuit board cover
spare parts
2 - Sensor kit
3 - Circuit board
Attention: when orde-
4 - Valve kit
ring spare parts, always
5 - Two-pieces joint with OR
state the position n°
6 - Cable bushings
from the diagram below
7 - Accumulator adapter
and the product code
8 - Water accumulator
number found in the
pressure- ow regulator
technical data table.
Article
CODE:
V00103101
V / Hz:
~230 / 50-60
I max:
16 A
Version
8
B
SN 1506003
Solutions
Check the electrical connections
Relocate PRESFLO
®
to another position
®
model with an inadequate
Install a model with a higher start-up pressure (Pm)
Check the electrical connections and that the pump
is working
®
"STAND-BY"
Reset PRESFLO
®
(See Operation, point 3).
®
in temporary shut down
Wait for the automatic restart or press START to
restart manually (See Operation, point 4a)
Replace the pump with one with more suitable
characteristics
Install a model with a lower start-up pressure (Pm)
Wait for the automatic restart or press START to
®
in temporary shut down
restart manually (See Operation, point 4b). Remove
any cause of leakage from system or install an
expansion tank
Check if the setting of the maximum current (Imax)
is congruent with the data of the pumps' rating
®
stops due to "OVERCUR-
plate. If after manually restarting the pump after
correctly setting PRESFLO
anomaly, check that the motor has no mechanical
or electrical problems.
®
's valve will not open
Check that the valve is not blocked by any foreign
objects and clean if necessary
Check the hydraulic connections and repair any
leaks. If a leak cannot be repaired, install an
expansion tank
Make sure that all taps are turned off and that
there are no leaks within the system
®
's check valve will not
Check that the valve is not blocked by any foreign
objects and clean if necessary
Dimensions
5
3
4
2
1
7
6
Con guration
Settable parameters:
- Running pressure.
When the pressure in the
system falls below the Pm,
®
PRESFLO
starts-up the pump.
The Pm should always be
higher by at least 0.2 – 0.3
bar of the pressure genera-
ted by the column of water
overlooking PRESFLO
The Pm value can be carried
in the eld between 1 bar and
5 bar.
- Maximum current
allowed.
PRESFLO
®
is tted with a cur-
rent sensor, which continually
detects the absorption of the
pump. If the current remains
above the set Imax value for
a signi cant period of time,
PRESFLO
®
stops the pump to
protect it from damages (LOCK
condition for OVERCURRENT).
®
PRESFLO
nevertheless allows
®
, it again signals an
the Imax to be exceeded for
short periods during the pump
start-up phase.
For correct functioning,
the Imax should be set at
a value higher by approx.
10 – 20% to the maximum
absorption of the pump
(normally indicated on the
rating plate of the motor).
If this rating value is not known,
it s better to leave the standard
Imax value (16A) to avoid that
the pump stops also in normal
absorption conditions.
The Imax value may be varied
in the eld between 4A and
16A.
Disposal
When disposing of any
PRESFLO
®
parts, adhere
to the relevant laws and
regulations in force in
the country in which the
equipment is being used.
Do not dispose of any
polluting parts in
the environment.
Manufacturer's setting:
PRESFLO
®
is supplied with the
following STANDARD CONFIGU-
RATION:
- Running pressure
Pm = 2 ( bar )
- Max. current allowed
I max = 16 ( A )
®
.
Con guration
1. Remove the small screwdri-
ver and adjust the trimmer on
The adjustment of the starting
the desired limits, according to
pressure (Pm) and the ma-
the values shown on the plate
ximum permissible current (I
located under the screwdriver.
max) is done by means of two
trimmers shown in FIG.
2. The start-up pressure can
be adjusted continuously from
1 to 5 bar (trimmer A)
Statement of Compliance: we declare, under our own respon-
sibility, that the product in question is in compliance with the fol-
lowing European Directives and national implementation provisions
2006/95/CEE Low Voltage Directive
Bigarello 27.05.15
2002/95/CEE (RoHS)
2002/96/CEE - 2003/108/CEE (WEEE)
DGFLOW S.r.l.
2004/108/CE Electromagnetic Compa-
President
tibility Directive (EMC)
Stefano Concini
EN 60730-2-6
EN 61000 6-3
3. The maximum permissible
current can be adjusted
continuously from 4 to 12 A
(trimmer B)
4. When you nish adjustment
close the cover