Room Entry Sensor (RMA-RE1-SEN)
2. Separate and strip the leads on the other end of the included speaker cable, exposing
about 1/2" of wire.
3. Twist the speaker cable leads with ½" exposed wire to the proximity
switch leads. The proximity switch is non-polarized, so you may
connect either side of the speaker cable to either side of the proximity
switch leads.
4. Cap or tape the connected leads to avoid a short.
5. Run the speaker cable back to your Room Alert. Try to avoid running it near large
electromagnetic devices or fluorescent lights, which produce EMI and can interfere with
sensor readings.
6. Connect the free ends (the 1/4" leads) of the speaker cable to an
open switch port on your Room Alert. Be sure the bare wire, not the
insulation, connects to the port. Again, the leads are non-polarized, so
you may connect either lead to either side of the open port.
Sensor Features & Specifications
Environment Condition Monitored
Type Of Sensor
Normal State
Alarm State
Sensor Cable Type
Included
Length
Maximum Extendible Length
Operating Temperature Range
Compatible Products
Proximity (Open/Closed)
Switch
Closed (Proximity switch & magnet together)
Open (Proximity switch & magnet apart)
Low-voltage two-wire speaker cable
Yes
25'
900'
-40º F to 221º F (-40º C to 105º C)
Any Room Alert model or Wireless Sensor Hub
Page 2
AVT-171211-2.1.0