ABB 4CKT COMBINER 1600312215A Краткое руководство по эксплуатации - Страница 3
Просмотреть онлайн или скачать pdf Краткое руководство по эксплуатации для Промышленное оборудование ABB 4CKT COMBINER 1600312215A. ABB 4CKT COMBINER 1600312215A 11 страниц. Power express 2 circuit and 4 circuit combiner
QUICK START GUIDE
Safety Statements
•
Do not install this equipment over combustible surfaces.
•
Rules and Regulations - Follow all national and local rules and regulations when making field connections.
•
Compression Connectors:
•
U. S. or Canada installations - use Listed/Certified compression connectors to terminate Listed/Certified field-
wire conductors where required.
•
All installations - apply the appropriate connector to the correct size conductor as specified by the connector
manufacturer, using only the connector manufacturer's recommended or approved tooling for that connector.
•
Electrical Connection Securing - Torque to the values specified on labels or in the product documentation.
•
Cable Dress - dress to avoid damage to the conductors and undue stress on the connectors.
•
Fuses and Circuit Breakers - Size as required by the National Electric Code (NEC) and/or local codes.
•
Refer to the equipment ratings to assure current does not exceed:
•
Continuous Load (List 1) - 60% of protector rating
•
Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.
•
Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations .
•
Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.
•
Size AC field-wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board circuit breaker
rating.
•
Size DC field-wired conductors with 90°C ampacity (NEC) equal to or greater than circuit breaker/fuse rating.
•
AC and DC input disconnect/protection - Provide accessible devices to remove input power in an emergency.
•
Alarm Signals - Provide external current limiting protection. Rating 60V, 0.5A unless otherwise noted.
•
Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the cabinet ac
service ground bus. In huts, vaults, and central offices connect to the system bonding network.
•
Circuit Breakers and Fuses - Use only those specified in the equipment ordering guide.
•
GMT Style Fuses - Use only fuses provided with safety caps.
Page 3
© 2021 ABB. All rights reserved.
Version 1.0