Dell E103S Руководство по установке и обслуживанию - Страница 27
Просмотреть онлайн или скачать pdf Руководство по установке и обслуживанию для Сервер Dell E103S. Dell E103S 34 страницы.
Figure 19. Removing a power supply unit blank
Next steps
Replace the
PSU
or
PSU
Removing a power supply unit
Prerequisites
CAUTION:
The system requires one power supply unit (PSU) for normal operation. On power-redundant
systems, remove and replace only one PSU at a time in a system that is powered on.
1. Follow the safety guidelines listed in the
2. Disconnect the power cable from the power outlet and from the Power Supply Unit (PSU) you intend to remove.
3. Remove the cable from the strap on the PSU handle.
NOTE:
The PowerEdge XR8000r only supports reverse air flow (RAF) Power Supply Units (PSUs). The PSUs with blue
straps are designed for reverse air flow (RAF).
NOTE:
For information about DC PSU cabling instructions, see the Cabling instructions for - (48 - 60) V DC power
supply Tech sheet that is shipped with your DC PSU or go to https://www.dell.com/poweredgemanuals > XR Servers >
PowerEdge XR8000r > Select This Product > Documentation > Manuals and Documents > Cabling instructions for - 48 - 60
V DC power supply.
Steps
Press the orange release latch, and holding the PSU handle slide the PSU out of the PSU bay.
blank.
Safety
instructions.
Installing and removing system components
27