Table 17. AC PSU status indicator codes
Power indicator codes
Green
Blinking amber
Not illuminated
Blinking green
Blinking green and turns
off
Figure 12. DC PSU status indicator
1. DC PSU status indicator
Table 18. DC PSU status indicator codes
Power indicator codes
Green
Blinking amber
Not illuminated
Condition
A valid power source is connected to the PSU and the PSU is operational.
Indicates a problem with the PSU.
Power is not connected to the PSU.
When the firmware of the PSU is being updated, the PSU handle blinks green.
CAUTION:
Do not disconnect the power cord or unplug the PSU when updating
firmware. If firmware update is interrupted, the PSUs do not function.
When hot-plugging a PSU, the PSU handle blinks green five times at a rate of 4 Hz and turns off.
This indicates a PSU mismatch with respect to efficiency, feature set, health status, or supported
voltage.
CAUTION:
If two PSUs are installed, both the PSUs must have the same type of label;
for example, Extended Power Performance (EPP) label. Mixing PSUs from previous
generations servers is not supported, even if the PSUs have the same power rating.
This results in a PSU mismatch condition or failure to turn the appliance on.
CAUTION:
When correcting a PSU mismatch, replace only the PSU with the blinking
indicator. Swapping the PSU to make a matched pair can result in an error condition
and unexpected appliance shutdown. To change from a high output configuration to a
low output configuration or vice versa, you must turn off the appliance.
CAUTION:
AC PSUs support both 240 V and 120 V input voltages with the exception of
Titanium PSUs, which support only 240 V. When two identical PSUs receive different
input voltages, they can output different wattages, and trigger a mismatch.
CAUTION:
If two PSUs are used, they must be of the same type and have the same
maximum output power.
CAUTION:
Combining AC and DC PSUs is not supported and triggers a mismatch.
Condition
A valid power source is connected to the PSU and the PSU is operational.
Indicates a problem with the PSU.
Power is not connected to the PSU.
Overview