Dell PowerEdge E31S Series Руководство пользователя - Страница 24

Просмотреть онлайн или скачать pdf Руководство пользователя для Сервер Dell PowerEdge E31S Series. Dell PowerEdge E31S Series 32 страницы.

Dell PowerEdge E31S Series Руководство пользователя
Expanded operating temperature
≤ 1% of annual operating hours
NOTE:
When operating in the expanded temperature range:
The performance of the appliance may be impacted.
The ambient temperature warnings may be reported in the System Event Log.

Expanded operating temperature restrictions

Do not perform a cold startup below 5°C.
The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft).
Redundant power supply units are required.
Non-Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.
The 3.5-inch hard drive chassis supports a maximum of 120 W processor.
The chassis supports a maximum of 145 W processor.
Only SSDs are allowed in the hard drive slots at the back of the chassis.
24
Technical specifications
Specifications
For temperatures between 35°C and 40°C, de-rate maximum
allowable temperature by 1°C per 175 m above 950 m (1°F per 319
ft).
–5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C
to 35°C), the appliance can operate down to –5°C or up
to 45°C for a maximum of 1% of its annual operating
hours.
For temperatures between 40°C and 45°C, de-rate maximum
allowable temperature by 1°C per 125 m above 950 m (1°F per 228
ft).