Dell SC180 Руководство пользователя - Страница 22

Просмотреть онлайн или скачать pdf Руководство пользователя для Хранение Dell SC180. Dell SC180 37 страниц. Storage center
Также для Dell SC180: Руководство пользователя (39 страниц)

Dell SC180 Руководство пользователя
Figure 13. Removing a Fan Module
1.
Fan module
2.
Rotate the replacement fan module so that the release tab and handle are on the right side.
3.
Slide the replacement fan module into the chassis until it is fully seated and the release tab clicks into
place.
NOTE: Allow several seconds for the enclosure to recognize the fan module and determine its
status. When functioning properly, the fan module's Module OK LED turns green and the
Battery fault and Fan fault LEDs are off. In addition, the cooling fan status indicator turns green
in the Dell Storage Client.
4.
In the Dell Storage Client, make sure that the replacement fan module is recognized and shown as
up and running.
Next steps
1.
Use SupportAssist to send diagnostic data to Dell Technical Support Services.
2.
Contact Dell Technical Support Services to let them know that you completed a repair.
22
2.
Release tab
Replacing SC180 Components