The SHM Monitor configuration file is located in the installation directory. The following is the default
location of the configuration files.
Table 30. Log File Location
Operating
Log File Location
System
Windows
C:\Program Files\Dell\ServerHardwareManager\ServerHardwareManagerMonitor
\SHM_Snmp.conf
Although the SHM Monitor runs automatically upon installation, you must configure a trap destination in
the configuration file for SNMP to function correctly. A trap destination has the following format:
ip=ipaddress[:port]
For example:
ip=192.168.1.1:1050
Address — The IP address of the destination
Port — Port on the target machine the trap receiver listens
Refer to the documentation of the trap listener for the port number it uses. If no port is specified, SHM
Monitor sends traps to the default port– 162.
NOTE: After any changes are made to the SNMP configuration file, you must stop and start the
service for changes to take effect.

Critical events

The SHM Monitor logs all event types. However, SNMP sends only critical events to the trap destination.
The list here outlines the critical events:
Power Supply Unit (PSU)
– PSU is removed
– DC voltage goes out of range of safe operating values
– DC current goes out of range of safe operating values
Fan is removed
Temperature Sensor
– Temperature of enclosure is above/below critical threshold
Voltage Sensor
– Voltage goes above or below a critical threshold
– AC power failure
– DC power failure
Drawer
– Drawer is opened