Dell Force10 C150 Краткое руководство по эксплуатации - Страница 10

Просмотреть онлайн или скачать pdf Краткое руководство по эксплуатации для Переключатель Dell Force10 C150. Dell Force10 C150 33 страницы. Quick start guide

Dell Force10 C150 Краткое руководство по эксплуатации
Attach a Ground Cable to the C150/300 DC
Chassis
WARNING: You must complete the ground connection before proceeding
with any DC PEM connection.
The AC power cord is the primary ground connection for C-Series AC chassis.
This procedure applies to the DC powered chassis only.
You must provide your own cables to connect to a remote power source (a
circuit breaker panel, for example) in your equipment rack or facility. Cables
must be sized to meet the following criteria:
Rated for 60A service to allow for a fully loaded C150 system per NEC in the
United States or internationally, per local safety codes.
Limit voltage drop across the cable length to 0.5V or less.
Apply a coat of anti-oxidant paste to unplated metal contact
NOTE:
surfaces before you make the cable connections. File unplated connectors,
braided straps, and bus bars to a shiny finish. It is not necessary to file and
coat tinned, solder plated, or silver-plated connectors or other plated
connection surfaces, such as those on the PEM studs.
Step
Task
Locate the chassis ground connector stud on the PEM front panel. It is
1
the single stud below the safety cover.
Remove the nut and washer from the ground stud.
2
Apply a coat of anti-oxidant paste to the connector stud, if required.
3
Install the grounding cable. This cable is typically green or green and
4
yellow.
Replace the washer and nut on the stud.
5
Secure the nut with a nut driver or torque wrench (not to exceed 4
6
ft/lbs).
Connect the opposite end of the grounding cable to the appropriate
7
nearest grounding.
8
Installing the Hardware
NOTE: Termination points require UL-listed 1-hole lug with a
1/4-inch hole.