Site Preparations
The Z9000 is suitable for installation as part of a common bond network (CBN).
You can install the system in:
•
network telecommunication facilities
•
data centers
•
other locations where the National Electric Code (NEC) applies
For more information about Z9000 specifications, refer to Specifications.
NOTE: Install the Z9000 system into a rack or cabinet before installing any optional components.
Site Selection
The following section describes where to install Dell Networking equipment.
Install Dell Networking equipment in restricted access areas. A restricted access area is one in which
access can only be gained by service personnel by using a special tool, lock, key or other means of
security and access is controlled by the authority responsible for the location.
Ensure that the area where you install your Z9000 system meets the following safety requirements:
•
Near an adequate power source. Connect the system to the appropriate branch circuit protection as
defined by your local electrical codes.
•
Environmental temperature between 32° to 104°F (from 0° to 40°C).
•
Relative humidity that does not exceed 85% noncondensing.
•
In a dry, clean, well-ventilated and temperature-controlled room, away from heat sources such as hot
air vents or direct sunlight.
•
Away from sources of severe electromagnetic noise.
•
Positioned in a rack or cabinet, or on a desktop with adequate space in the front, rear, and sides of the
Z9000 for proper ventilation and access.
Cabinet Placement
Install the Z9000 only in indoor cabinets designed for use in a controlled environment.
Do not install the Z9000 in outside plant cabinets. For cabinet placement requirements, refer to
Selection.
The cabinet must be a minimum cabinet size. Airflow must be according to the Electronic Industries
Alliance (EIA) standard. Ensure that there is a minimum of five inches (12.7 cm) between the intake and
exhaust vents and the cabinet wall.