Allmand 10-000001 Краткое руководство по эксплуатации - Страница 5

Просмотреть онлайн или скачать pdf Краткое руководство по эксплуатации для Промышленное оборудование Allmand 10-000001. Allmand 10-000001 17 страниц.

Allmand 10-000001 Краткое руководство по эксплуатации
MAXI LITE II 
SERIAL NUMBER 10-000001 & 11-000001 
Test the power output at the GFCI receptacle, while the engine is running and the main
breaker and receptacle breaker is switched to the "ON" position.
Set the multimeter to the AC volt position and insert the probe tips into the hot and
neutral sides of the GFCI receptacle.(See figure ​ A ​ b elow​ )
A meter reading of 120.0 volts +10% indicates that the generator is operating properly.
Refer to page 2. For further troubleshooting procedures.
A reading less than 120 volts + 10% indicates that the generator may be malfunctioning,
or there can be an issue with the main circuit breaker, pop out receptacle circuit
breaker, GFCI receptacle by itself, or the wiring between any of these. Refer to page 2
for additional troubleshooting.
NOTE: Many Allmand light towers designed for use outside North America operate at 230 volts/
50 Hz. Testing is done the same way following the above instructions. If you are unsure which
voltage your light tower is designed to produce contact a qualified electrician for assistance.
Figure A.1