No Power To IQ Control
**Maxi Heat 500IQ Controller does not turn on or has no power to the IQ box.**
❏ No power into the IQ controller will not activate the LCD screen for further
operation. Make sure the door on the outlet (heat out of burner) side is
open. The micro switch in the corner of the door activates power to each
screen. * Switch is a two pole switch, if one side fails then the other could
still open and provide power to the other screen.*
❏ Check the relay in the transformer box next to the controller (Example
"A"). Make sure connections are secure and the relay is functioning
properly.
❏ Check the heater element on top of the fuel water separator filter. If
element shorts then it will draw too much amperage and not allow the
screen to power up.
❏ If the IQ controller has 12 volts on the two wire ( example "B" below)
harnesses into the side of the controller. If the wire has 12 volts then the
screen needs to be replaced.
❏
Example "B"
M axi Heat 500IQ
Example "A "