⑤ Anti-vibration assembly.
⑥ Note direction of water flow.
⑦ Connect the 9mm o/d x 6mm i/d tube from the reservoir to the pump.
Ensure the length of the tube is less than 2 meters (6.5ft) and secure with
cable ties.
⑧ Connect your 9mm o/d x 6mm i/d vinyl discharge tube to the outlet barb on
the pump and secure with a cable tie. Direct discharge tube to a proper
drainage outlet. Ensure discharge tube does not have kinks or constrictions.
-05-
⑨ A high-level alarm switch should be wired into the air conditioning signal
wire, to stop the operation of the air conditioning unit in the event of a pump
failure.
N.C.
Indoor unit
COM
N.O.
Alarm/Volt Free
Condensate pump
L N E
L N E
CAUTION
Use the wiring diagram above to ensure correct wiring connection.
⑩ Test pump operation by pouring water into evaporator tray. Check for leaks.
Outdoor unit
L N E
-06-
-06-